Connection of separate systems, 1 general, 2 cable marking – KROHNE OPTISONIC 6300 EEx EN User Manual

Page 13: 3 cable parameters, 4 equipotential bonding

background image

CONNECTION OF SEPARATE SYSTEMS

3

13

OPTISONIC 6300

www.krohne.com

03/2010 - 7309972300 - EX OPTISONIC 6300 R03 en

3.1 General

The electrical connection between the ultrasonic flow sensor and the signal converter is
established with MR 02 - RGX 316 triax signal cable. The ends of the coaxial cables are provided
with SMB plugs. The signal cable is provided with the system.

3.2 Cable marking

Please refer to

Signal cable connections

on page 14 for the connection of the different versions.

3.3 Cable parameters

The maximum permitted total capacitance and inductance for the connecting cable is:

C

L

= 1,29 μF or 0,79 μF

L

L

= 0,1 mH or 0,8 mH

The cable supplied with the instrument has the following parameters:
distributed capacitance C

C

(core/screen) = 94 pF/m

distributed inductance L

C

(core/screen) = 0,24 μH/m

3.4 Equipotential bonding

3.4.1 Signal converter

The UFC 300 F(/i)-Ex ultrasonic signal converter must always

must always

must always

must always be incorporated within the

equipotential bonding system of the installation in the hazardous classified location. For this
purpose it must be connected to the external U-clamp screw terminal (size M5) on the wall-
mounting device.

The separate bonding conductor must be at least 4 mm

2

(11 AWG) or 2.5 mm

2

(14 AWG) in case it

is mechanically protected, see Clause 413 of HD 384.4.41 or IEC 364-4-41. Make sure that the
core of the bonding wire is properly mounted under the U-clamp of the external M5 terminal and
that the screw is tightly fixed.

3.4.2 Flow sensor

The intrinsically safe transducer circuits of the flow sensor are galvanically isolated from earth,
therefore an equipotential bonding conductor between the flow sensor and the signal converter
does not have to be connected.

INFORMATION!
The standard length of the signal cable is 5 m. In case a longer length is required, please contact
your local representative for detailed information.