beautypg.com

Device description, 8 electrical data – KROHNE H250 M40 ATEX II3G Ex nA EN User Manual

Page 14

background image

2

DEVICE DESCRIPTION

14

H250 M40

www.krohne.com

01/2012 - 4001485201- MA H250/M40-Ex-II3G-AD R01 en

Maximum permitted temperatures at reference point of indicator in °F

2.8 Electrical data

Design of
indicator

Component

Permitted temperature range at reference point T [°F] according to
temperature class

TK T6

T5

T4 ... T1

M40./../K.

SC3,5-NO-Y

-4 ... +149

-4 ... +176

-4 ... +194

SJ3,5-SN

-4 ... +151

-4 ... +178

-4 ... +194

SJ3,5-S1N

-4 ... +151

-4 ... +178

-4 ... +194

I7S23,5-N

-40 ... +158

-40 ... +185

-40 ... +194

M40./../ESK4/K.

SC3,5-NO-Y

-4 ... +131

-4 ... +158

-4 ... +176

SJ3,5-SN

-4 ... +131

-4 ... +158

-4 ... +176

SJ3,5-S1N

-4 ... +131

-4 ... +158

-4 ... +176

I7S23,5-N

-40 ... +131

-40 ... +158

-40 ... +176

M40./../ESK4

ESK4

-40 ... +131

-40 ... +158

-40 ... +176

M40./../ESK4-T

ESK4 and I/O modul

-40 ... +126

-40 ... +153

-40 ... +171

M40./../ESK4-FF

ESK4 and ESK4-FF

-40 ... +97

-40 ... +124

-40 ... +169

M40./../ESK4-PA

ESK4 and ESK4-PA

Electrical equipment

Rated voltage

Nominal current

Limit switch K1 / K2

8 VDC

≤1 / ≥3 mA

Signal output ESK4

14 - 32 VDC

4...20mA with HART

®

communication

Switching output ESK4-T OC output

8 - 32 VDC

1...100 mA

Switching output ESK4-T NAMUR output 8 VDC

≤1 / ≥3 mA

Signal input ESK4-T input

8 - 32 VDC

≤2 mA

ESK4-FF Foundation Fieldbus

transmitter

1

9 - 32 VDC

16 mA

ESK4-PA Profibus transmitter

2

9 - 32 VDC

16 mA

1 Further information and instructions for operation of the ESK4-FF transmitter are provided in separate supplementary

instructions.

2 Further information and instructions for operation of the ESK4-PA Profibus transmitter are provided in separate sup-

plementary instructions.