Roughneck, Block diagram – Detcon H2S RoughNECK User Manual
Page 3
3.0 I
NTERFERENCE
D
ATA
Detcon RoughNECK™ H2S sensors are designed to detect and monitor hydrogen sulfide gas in ambient
air in the range of 0-100 parts per million. Minimum sensitivity and scale resolution is 1 ppm. Sensor spec-
ifications reflect an operating temperature range of -40° F. to +175° F. While the sensor is capable of operat-
ing outside these temperatures, performance specifications are verified within the limit.
Interference Data
Methane
25,000 = 0
Ethane
5,000 = 0
Hexane
5,000 = 0
Propane
5,000 = 0
Butane
5,000 = 0
Carbon Monoxide
800 = 0
Carbon Dioxide
5,000 = 0
Carbon Disulfide
14 = 0
Methonol
200 = 0
Isopropanol
200 = 0
Ammonia
500 = 0
Diesel Fuel
= 0
Demethyl Sulfide
4.4 = 0
Ethylene
200 = 0
Freon 12
1000 = 0
Hydrogen
1000 = 8
Methyl Mercaptan
5 = 8
Sulfur Dioxide
300 = 0
Toluene
32 = 0
Ethanol
200 = 0
4.0 S
PECIFICATIONS
Method of Detection
Solid state metal oxide. Diffusion/adsorption
Electrical Classification
NEMA 4 Non-Hazardous controller; NEMA 7 sensor
Response Time
80% < 2 minutes
Clearing Time
Detcon RoughNECK™ H2S Gas Detection & Alarm System PG.3
Pre-amp
(span)
Constant
Temperature
Control
MOS
Sensor
RTD
Heater
Alarm &
Signal
Conditioning
Power In
Low
Alarm
Strobe
High
Alarm
Horn
RoughNECK
™
Block Diagram