CAPACITY: 16 Single Channels
POWER: 24 VDC Input to Controller Motherboard
ALARM CONTACTS: Discreet Fault, Low, High, per Channel 2 Amp @ 30VDC/.6 Amp @ 125VAC

Common, Normally Open and Normally Closed

OUTPUTS: Discreet 4-20 MADC
OPERATING TEMPERATURE RANGE: -40°F to +175°F
POWER CONSUMPTION: <5 Watts per Channel

1.3 REMOTE RESET

The reset function is effective when the Model 10A's respective alarms have been pro-

grammed in the latching position and alarm conditions have passed. The alarm reset function is
common to all controllers and is activated by closing the circuit between the two reset contacts.
A normally open momentary switch is suitable.

1.4 INSTALLATION

01. Securely mount the 1610A rack enclosure in accordance with the drawing in figure 1.
02. Connect 24 VDC input wiring to the lugless terminal strip (labeled DC IN) on the back of the

controller mother board (see fig 2).

Caution: Observe correct polarity when terminating all input/output field wiring. Failure
to do so may result in circuit damage on power up.

04. If applicable, connect a normally open momentary remote mounted switch to the lugless

terminal strip (labeled RESET) located on the controller mother board (see fig 2).

05. Refer to installation and wiring detail of remote mount sensor assemblies as detailed in

section 3.0. Terminate field wiring from sensors to Model 1610A rack lugless terminal strips
located on the controller mother board (see fig 2).

Note: Based on the application and use of relay contact outputs, complete all wiring
terminations prior to application of power. Shut-in controls may be omitted until system
test is complete.

1.5 START-UP

Upon completion of all field wiring apply 24VDC power to the 1610A rack. Note that each

Model 10A controller digital display illuminates. Varying readings may occur during sensor
warm-up. A 10 second alarm delay will occur on power up. Refer to sections 2.0 and 3.0 for
additional start-up detail.

1.6 SPARE PARTS

0224

Gold plated jumper tab

1.7 WARRANTY

Detcon inc., as manufacturer, warrants under intended normal use each new Model 1610A

rack control enclosure to be free from defects in material and workmanship for a period of one
year. The warranty period begins from the date of shipment to the original purchaser and ends
one year thereafter. All warranties and service policies are FOB the Detcon Inc. facility located in
The Woodlands, Texas.