Calibration, Figure 2 cut-out template figure 3 dimensional, 0 calibration – Detcon 100 Duct Mount Kit User Manual
Page 4: Figure 2 cut-out template, Figure 3 dimensional
100 Duct Mount
100 Series Duct Mount Kit
Rev. 0.1
Page 2 of 4
3.125"
3"
5"
4.25"
Mounting Holes
Figure 2 Cut-out Template
16.3"
3"
7"
5"
D ETCON, INC .
H2S
100 PPM
DM-100
Model 100
CAL PORT
5"
6.15"
6.5"
Duct side
wall
Mounting Hardware
Figure 3 Dimensional
3.0 Calibration
CAUTION: In high velocity air ducts, air flow may need to be shut down before calibration takes place.
1 - Verify that there is no air flow through the duct.
2 - Remove the cal port plug.
3 - Apply the target gas to the cal port at a flow rate of 500 milliliter per minute for combustible (FP series)
and solid state H2S (TP series) sensors. Apply a flow rate of 1000 ml/m for toxic gas (DM series) sensors.
Refer to the sensor manual for more information on the sensor calibration.
4 - Follow calibration instructions provided in the sensor instruction manual.