Calibration, Figure 2 cut-out template figure 3 dimensional, 0 calibration – Detcon 100 Duct Mount Kit User Manual

Page 4: Figure 2 cut-out template, Figure 3 dimensional

background image

100 Duct Mount

100 Series Duct Mount Kit

Rev. 0.1

Page 2 of 4

3.125"

3"

5"

4.25"

Mounting Holes

Figure 2 Cut-out Template

16.3"

3"

7"

5"

D ETCON, INC .

H2S

100 PPM

DM-100

Model 100

CAL PORT

5"

6.15"

6.5"

Duct side
wall

Mounting Hardware

Figure 3 Dimensional

3.0 Calibration

CAUTION: In high velocity air ducts, air flow may need to be shut down before calibration takes place.
1 - Verify that there is no air flow through the duct.
2 - Remove the cal port plug.
3 - Apply the target gas to the cal port at a flow rate of 500 milliliter per minute for combustible (FP series)
and solid state H2S (TP series) sensors. Apply a flow rate of 1000 ml/m for toxic gas (DM series) sensors.
Refer to the sensor manual for more information on the sensor calibration.
4 - Follow calibration instructions provided in the sensor instruction manual.