Aluminum Junction Box


Aluminum Junction Box

PN 897-850901-010 (Glass Lens version)
PN 897-850000-010 (Solid cover version)

This product is for use as a stand-alone certified junction box or for use in product applications where a
certified XP component junction box is part of a more advanced product package.

The Ratings are as follows:

Class 1, Division 1, Groups BCD
II 2 G Ex d IIB+H2
Ta -40ºC to 75ºC

Figure 1 Aluminum Condulet Approvals label


The ratings comply with EN 60079-0-2006 and EN 60079-1-2007 standards.

NOTE: Properly rated ¾” NPT blanking plugs must be installed on any conduit entry that is
not used. The blanking plugs shall be approved components and shall have hazardous location
ratings that are rated equal or greater than the junction box.


NOTE: All component types that may be attached to this ATEX and

c

CSA

us

certified junction

box shall be approved components and shall have hazardous location ratings that are rated
equal to or greater than the junction box.



Special Conditions for Safe Use:

1. The equipment is only to be used in Zone 1 and Zone 2 hazardous locations.
2. Where necessary for safety, the contents of the enclosure shall comply with the appropriate

requirements of relevant standards for electrical apparatus for use in potentially explosive
atmospheres.

3. The assembled equipment shall comply with the appropriate requirements of relevant standards for

electrical apparatus for use in potentially explosive atmospheres.

4. The enclosed apparatus may be placed in any arrangement provided that an area of at least 20% of

each cross sectional area remains free to permit unimpeded gas flow and therefore unrestricted
development of an explosion.

5. Rotating or other devices creating turbulence shall not be incorporated.

Detcon J-Box Instruction Manual

Rev. 0.0