700 RAM I.M.

necessary to install/use the Transient Protection Module shipped with the 700 sensor. The 700 sensor may
arrive from the factory pre-assembled with the RAM in the j-box, but only if it is ordered in this
configuration. In this configuration, the wires from the 700 sensor will be directly connected to the 6-pin
terminal block labeled “SENSOR” on the terminal board.

NOTE: If the 700 sensor and RAM are directly connected, it is not necessary to install/use the
Transient Protection Module that is shipped with every 700 Gas Sensor.

PGM2

SPAN

detcon inc.

MODEL

XX-700

PGM1

ZERO

Sensor

Power Input

mA Output

Modbus

Interface

Fault

Annunciator

Alarm 1
Annunciator

Alarm 2
Annunciator

Figure 6 Installation with 700 Gas Sensor


If remote sensor separation is required, the RAM will be separated from the 700 sensor. Remote separation
distances of up to 1000 feet are possible with the recommended cables.

NOTE: It is highly recommended to install the interconnecting cabling inside rigid metal
conduit to eliminate potential EMI and RFI interference.

mA Output

700 RAM

Module

Cabling to/from

Remote 700 Sensor

Remote 700 Sensor

Transient Protection

Module in Detcon

standard J-Box

Power Input

Sensor

detcon inc.

MODEL
XX-700

PGM1

ZERO

PGM2

SPAN

Modbus

Interface

Power & Modbus

Figure 7 Remote 700 Gas Sensor with RAM


The recommended cable for remote sensor separation is Belden 8770 (18AWG shielded 3-wire cable) for
connection of power and mA signal return and Belden 9841 (24AWG shielded twisted pair) for serial
Modbus™ communications.

700 RAM I.M.

Rev. 1.0