700 RAM I.M.

junction box via two machine screws allowing the RAM display and RAM connector board to unseat from
the 12-pin plug-in connector and provide access to the terminal board connectors (Figure 5). To install the
electronics package, properly align the 12-pin plug-in connector and gently push the RAM in until it is fully
seated to the terminal board. The RAM faceplate will be even with the top of the junction box when installed
properly. The RAM top should be flush with the top of the enclosure before screwing down the junction box
cover.

The RAM display and

RAM connector board

External Wiring

12-Pin Plug-In

Connector

Input Port

The terminal

board sets on

the stand-offs in

the enclosure

Provide at least

a 6" Service
Loop for all
wiring

6"

Input Port

Note: Retaining Guard
removed for clarity

RAM faceplate

Explosion Proof Junction Box

Figure 4 Exploded View of Assembly

1.3 Field Wiring

The field wiring connections are made to the bottom PCA (terminal board) of the RAM using a series of
connector blocks. There is a 6-pin terminal block for connection to the 700 Gas Sensor (labeled SENSOR), a
9-pin terminal block for connection to the 3 relay contacts (labeled RELAY OUTPUT), a 6-pin terminal
block for connection of power, mA output and Modbus™ interface to the host device (labeled IN) and a 6-
pin terminal block for connection of power and Modbus™ interface to an additional device (labeled OUT).

700 Sensor

Connections

ALM1

ALM2

FLT

NO NC COM NO NC COM NO NC COM

J7

J2

J1

J4

IN

SENSOR

OUT

+

+

mA

A

B

mA

A

B

+

A

B

K1

K3

K2

Input Power and

mA Output

Alarm Relay

Connections

Output

Power

Modbus

Interface to Host

Modbus

Interface

U1

Figure 5 Interface connections on terminal board


The user will typically connect the 700 Gas Sensor directly to the RAM if there is no requirement for remote
sensor separation (Figure 6). In this case, the 700 sensor will not require its own junction box and it is not

700 RAM I.M.

Rev. 1.0

Page 3 of 13