beautypg.com

0 installation, Installation, Figure 3 dimensional – Detcon AV2-C1D2C User Manual

Page 7

background image

AV2-C1D2C

AV2-C1D2C Instruction Manual

Rev. 2.0

Page 3 of 4

2.0 Installation


The assembly is mounted on a T-shaped Aluminum bracket with holes pre-drilled to accommodate (2) U-bolt
attachments on a 2.5” maximum diameter pipe. U-bolt size is 3/8-16 x 3 inch. Overall Dimensions are 33”H
x 16.5”W x 18.5”D (Figure 3).

The alarm comes pre-wired for the voltage ordered from the factory (110 or 220VAC). Wiring is installed
through the opening at bottom of junction box. Connect wiring in accordance with the wiring diagram shown
in Figure 4. To determine the proper voltage of the strobe and siren, refer to the specifications label on the
alarm system enclosure. Use only 12 to 18 AWG wire for power connections. Strip no more than 0.25-inch of
insulation from the ends of the power leads. Ground can be connected either to the Condulet Ground Screw or
to the Plug on the terminal board. Optionally, each annunciator can be powered independently by removing
the jumper between terminal points 5, 6, and 7, and wiring directly to the return path of the annunciator.



21"

Typ.

16.5"

3.4"

8.3"

16"

5.5"

Figure 3 Dimensional