2 horn, Horn, Figure 2 horn – Detcon AV2-C1D2C User Manual
Page 6

AV2-C1D2C
AV2-C1D2C Instruction Manual
Rev. 2.0
Page 2 of 4
Enclosure Rating
Type 4X, IP66
Height 8.75in 
Diameter 5.5in. 
 
1.2 Horn
The alarm station vibratone® horn produces a noise level of a 100dB of sound by the electromechanical 
vibration of a stainless steel diaphragm. The horn mechanism with diaphragm is attached to the grill and has 
an effective broadcast range of 200 feet. The rugged water and dust tight backbox is ideal for indoor and 
outdoor use. 
 
The horn is capable of producing coded blasts or sustained tones, and is excellent for general alarm, 
start/dismissal, coded paging and process control signaling in areas where their sound output exceeds ambient 
noise levels. 
 
The hazardous location warning horn is available in voltage ratings of 120VAC or 240VAC-50/60Hz. and 
accommodates surface, flush or semi-flush mounting on walls, panels, or in cabinets. The horn uses a compact 
sized die-cast zinc housing with a corrosion resistant polyurethane finish. The rugged outer grill resists 
vandalism without reducing sound output. UL listed and CSA certified for Class I, Division 2, Groups A, B, C 
and D; Class II, Division 2, Groups F, and G; and Class III. 
 
 
Figure 2 Horn
 
Specifications 
Voltage 
120VAC 50/60HZ, 240VAC 50/60HZ 
(see specifications label for voltage rating) 
Mount
Surface / Panel
Operating Current
0.18 Amps at 120VAC, 0.09 Amps at 240VAC
Operating Temperature Minimum
-65°F
Operating Temperature Maximum
150°F
Db Output
100db @ 10 feet, 110db @ 1 meter
Duty Cycle
Not rated for continuous duty
Enclosure Rating
Type 4X
Height 5.3in. 
Width 
5.3in. – 6in. to outside of mounting ears
Depth 3.66in. 
 
 
 