1.0 Description
The Detcon AV1-DV2, V2-DV2, and A1-DV2 Alarm Stations are wireless, battery powered alarm stations
with a 5 Joule Strobe and an 115Db @ 1mtr Horn. The AV1-DV2 uses a Horn and a Strobe, the V2-DV2 uses
2 Strobes, and the A1-DV2 uses a single Horn. The unit is designed for installation and use in Hazardous
duty, corrosive work environments rated at Class 1, Division 2, Groups E, F, and G.
AV1-DV2
Strobe Horn Combo
Alarm Station
V2-DV2
Dual Strobe
Alarm Station
A1-DV2
Horn Only
Alarm Station
Figure 1 Basic C1D2 Wireless Alarm Stations
The alarm station can be positioned almost anywhere, since the wireless ability of the unit means that there is
no need for running conduit or outside connections. The alarm station is powered by its internal 12V battery
pack. Communication is performed via the Detcon RXT-300 or RXT-320 series of transceivers. Access to the
unit is only necessary for battery maintenance or exchange. With the addition of a solar panel, access can be
kept to periodic functional tests and checks.
Internal wiring between components runs through the Wireless Alarm Interconnect PCA. This PCA controls
the state of the alarms via communication with the Wireless Transceiver. When an alarm is triggered, the
wireless transceiver will provide the interconnect PCA with the signal(s) necessary to activate the proper
alarm(s).
Alarm 2
wiring
Alarm 1
wiring
wiring to/from
Transciever
wiring to/from
Transciever
External
24VDC
connections
Rotary Switch
for Modbus
Address
012
3
4
5
678
9A
B
C
D
EF
Figure 2 Wireless Interconnect PCA