3.4.3 Program Mode

The program mode provides a program status menu, allows for the adjustment of alarm set point levels, and the

selection of the calibration gas level setting..

3.4.3.1 Program Status

The program status scrolls through a menu that displays:

* The gas type, range of detection and software version number. The menu item appears as:

“LEL 0-100 V6.0”

* The calibration gas level setting. The menu item appears as:

“CalLevel @ xx%”

* Sensor temperature in °C appears as:

“TEMPERATURE xx °C”

* The estimated remaining sensor life. The menu item appears as:

“OPTICS AT 100%”

3.4.3.2 Calibration Level Adjustment

The Calibration level is adjustable from 10% to 90% LEL. The menu item appears as:

“CalLevel @ ##%”

3.5 I

NSTALLATION

Optimum performance of ambient air/gas sensor devices is directly relative to proper location and installation practice.

3.5.1 Field Wiring Table (4-20 mA output)

Detcon Model IR-522 combustible gas sensor assemblies require three conductor connection between power sup-

plies and host electronic controllers. Wiring designators are + (DC), (DC) , and mA (sensor signal). Maximum

single conductor resistance between sensor and controller is 10 ohms. Maximum wire size for termination in the

sensor assembly terminal board is 14 gauge.

AWG

Meters

Feet

20

240

800

18

360

1200

16

600

2000

14

900

3000

Note 1: This wiring table is based on stranded tinned copper wire and is designed to serve as a reference only.

Note 2:

Shielded cable may be required in installations where cable trays or conduit runs include high voltage

lines or other sources of induced interference.

Note 3:

The supply of power must be from an isolating source with over-current protection as follows:

AWG

Over-current Protection

AWG

Over-current Protection

22

3A

16

10A

20

5A

14

20A

18

7A

12

25A

The RS-485 (if applicable) requires 24 gauge, two conductor, shielded, twisted pair cable between sensor and host

PC. Use Belden part number 9841. Two sets of terminals are located on the connector board to facilitate serial loop

wiring from sensor to sensor. Wiring designators are A & B (IN) and A & B (OUT).

3.5.2 Sensor Location

Selection of sensor location is critical to the overall safe performance of the product. Five factors play an important

role in selection of sensor locations:

(1) Density of the gas to be detected

(2) Most probable leak sources within the industrial process

(3) Ventilation or prevailing wind conditions

(4) Personnel exposure

(5) Maintenance access

Model IR-522 Combustible Hydrocarbon Sensor PG.8