Electrical Classification

Class I; Groups B, C, D; Div. 1.

Response Time

T50 < 15 seconds; T90 < 35 seconds

Clearing Time

90% < 35 seconds

Repeatability

± 3% FS

Range

0-100% (lower explosive limit) LEL

Operating Temperature

-40° to +175° F

Accuracy

± 3% FS

Sensor Warranty

5 year pro-rated

Power Consumption

Normal operation = 86 mA (2.1 watts); Max = 102 mA (<2.5 watts)

Zero Drift

< 5% per year

Output

Linear 4-20 mA DC

Input Voltage

11-28 VDC

3.4 O

PERATING

S

OFTWARE

Operating software is menu listed with operator interface via the two magnetic program switches located under the

face plate. The two switches are referred to as “PGM 1” and “PGM 2”. The menu list consists of 3 items which

include sub-menus as indicated below. (Note: see the last page of this manual for a complete software f low chart.)

01.

Normal Operation

a) Current Status

02.

Calibration Mode

a) Zero

b) Span

03.

Program Menu

a) Program Status

b) Calibration Level

3.4.1 Normal Operation

In normal operation, the display tracks the current status of the sensor and gas concentration and appears as:
“0 % LEL”. The mA current output corresponds to the monitoring level and range of 0-100% = 4-20 mA.

3.4.2 Calibration Mode

Calibration mode allows for sensor zero and span adjustments.

“1-ZERO 2-SPAN”

3.4.2.1 Zero Adjustment

Zero is set in ambient air with no combustible gas present or with zero gas applied to the sensor.

“AUTO ZERO”

3.4.2.2 Span Adjustment

Unless otherwise specif ied, span adjustment is performed at 50% LEL methane in air.

“AUTO SPAN”

Model IR-522 Combustible Hydrocarbon Sensor PG.7