Triangle Engineering of Arkansas Automatic Ceiling Shutter Information User Manual
Automatic ceiling shutter information
Automatic Ceiling Shutter Information
EXHAUST AIR:
Openings in the
attic area are nec-
essary to allow
the hot exhaust
air to escape. This
chart will help
you determine the
MINIMUM exhaust
area that is essential
to proper operation:
INLET AIR:
The windows in
the house should be opened in each room which
you wish to cool. The amount of moving air in
a particular room and velocity at which this air
CLOSED POSITION
Tie Bar with
adjusting holes
Shutter Blades
OPEN POSITION (75
°)
Make fine shutter adjustments by using holes in spring post and tie bar.
Spring
Spring
Spring Post with
four adjusting holes
Blocking
Ceiling
Tie Bar
Shutter
Frame
Shutter Frame
Blocking
Ceiling
Min. Free Exhaust
Model
Area Req'd.
CA 2421
8 sq. ft.
CA 3021
10 sq. ft.
CC 2422
8 sq. ft.
CC 3022
10 sq. ft.
CC 3023
11 sq. ft.
CC 3622
12 sq. ft.
CC 3623
16 sq. ft.
CC 4223
18 sq. ft.
CC 4823
22 sq. ft.
moves can be obtained by changing the window
opening.
PROPER MOUNTING OF
SHUTTER ASSIST SPRING:
The function of the spring included with your
shutter is to assist the shutter to open completely.
Because of the variety of shutter models, weights,
sizes, etc., there are several holes in which the
spring can be inserted.
To help identify which holes will be proper for the
shutter as it is applied in your home, open the shut-
ter to about 75° and insert the spring in the holes
as indicated in sketch below. If spring is too tight,
the shutter will not close. If too loose, the shutter
will not open properly. Be sure the shutter does not
open over 75° or it may not have enough weight to
pull itself closed.