beautypg.com

Triangle Engineering of Arkansas Automatic Ceiling Shutter Information User Manual

Automatic ceiling shutter information

background image

Automatic Ceiling Shutter Information

EXHAUST AIR:

Openings in the

attic area are nec-
essary to allow
the hot exhaust
air to escape. This
chart will help
you determine the
MINIMUM exhaust
area that is essential
to proper operation:

INLET AIR:

The windows in

the house should be opened in each room which
you wish to cool. The amount of moving air in
a particular room and velocity at which this air

CLOSED POSITION

Tie Bar with

adjusting holes

Shutter Blades

OPEN POSITION (75

°)

Make fine shutter adjustments by using holes in spring post and tie bar.

Spring

Spring

Spring Post with

four adjusting holes

Blocking

Ceiling

Tie Bar

Shutter

Frame

Shutter Frame

Blocking

Ceiling

Min. Free Exhaust

Model

Area Req'd.

CA 2421

8 sq. ft.

CA 3021

10 sq. ft.

CC 2422

8 sq. ft.

CC 3022

10 sq. ft.

CC 3023

11 sq. ft.

CC 3622

12 sq. ft.

CC 3623

16 sq. ft.

CC 4223

18 sq. ft.

CC 4823

22 sq. ft.

moves can be obtained by changing the window
opening.

PROPER MOUNTING OF
SHUTTER ASSIST SPRING:

The function of the spring included with your

shutter is to assist the shutter to open completely.
Because of the variety of shutter models, weights,
sizes, etc., there are several holes in which the
spring can be inserted.

To help identify which holes will be proper for the

shutter as it is applied in your home, open the shut-
ter to about 75° and insert the spring in the holes
as indicated in sketch below. If spring is too tight,
the shutter will not close. If too loose, the shutter
will not open properly. Be sure the shutter does not
open over 75° or it may not have enough weight to
pull itself closed.