Page 15: Connection of ranger 8+ diesel to premises wiring, Ranger 8+ diesel

background image

RANGER 8+ DIESEL

A-7

INSTALLATION

A-7

Connection of RANGER 8+ DIESEL to premises
wiring must be done by a licensed electrician and
must comply with the National Electrical Code and
all other applicable electrical codes.

230 Volt

60 Hz.

3-Wire

Service

POWER

COMPANY

METER

230 VOLT

115 VOLT

115 VOLT

LOAD

N

NEUTRAL
BUS

GROUND

PREMISES

DISCONNECT AND

SERVICE

OVERCURRENT

PROTECTION

GND

N

NOTE: No. 8 COPPER CONDUCTOR CABLE SEE

NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE

SIZE RECOMMENDATIONS.

230 VOLT

GROUNDED CONDUCTOR

40AMP

230 VOLT

DOUBLE

POLE

CIRCUIT

BREAKER

DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

50 AMP, 115/230

VOLT PLUG

NEMA TYPE 14-50

50 AMP, 115/230 VOLT

RECEPTACLE

Figure A.1

CONNECTION OF RANGER 8+ DIESEL TO PREMISES WIRING