beautypg.com

Troubleshooting, Caution – Lincoln Electric IM848 POWER WAVE AC_DC 1000 User Manual

Page 60

background image

E-9

TROUBLESHOOTING

E-9

POWER WAVE® AC/DC 1000

Observe all Safety Guidelines detailed throughout this manual

If for any reason you do not understand the test procedures or are unable to perform the tests/repairs safely, contact your
Local Lincoln Authorized Field Service Facility for technical troubleshooting assistance before you proceed.

CAUTION

PROBLEMS

(SYMPTOMS)

POSSIBLE

CAUSE

RECOMMENDED

COURSE OF ACTION

Analog Inputs donʼt respond or donʼt
respond quickly.

Gas purge not working.

1. Analog Scans Between Updates.

2. Analog In Active Selections.

3. Analog Hysteresis.

4. Passive Mode.

1. Out of gas.

2. Gas Purge not asserted.

3. Passive Mode.

4. Gas Lines.

1. The DeviceNet tab of the

Diagnostics Utility displays the
Power Waveʼs "Analog Scans
Between Updates" and "I/O
Scans/Sec." Verify that "Analog
Scans Between Updates" is 1/4
of "I/O Scans/Sec" value.

2. From the DeviceNet tab of the

Diagnostics Utility, select
Configure. Verify in "Analog Input
Channels" that the required
channels are set active.

3. From the DeviceNet tab of the

Diagnostics Utility, select
Configure. Verify in "Analog Input
Channels" that the Hysteresis
settings are all 0.

4. The DeviceNet tab of the

Diagnostics Utility displays the
Power Waveʼs passive mode
status. If the status needs to be
changed, select Configure, and
make the necessary modifica-
tion.

1. Verify there is gas available at

the input of the gas solenoid.

2. From the DeviceNet tab of the

Diagnostics Utility, select
Monitor. The Monitor window will
be displayed. Verify under the
"Produced Assembly" that "Gas
Purge" is highlighted.

3. The DeviceNet tab of the

Diagnostics Utility displays the
Power Waveʼs passive mode
status. If the status needs to be
changed, select Configure, and
make the necessary modifica-
tion.

4. Verify nothing is obstructing the

flow of gas.

DEVICENET-PLC CONTROLLED SYSTEM