Low Battery Warning.

PowerChute interface
software provides auto-
matic, unattended shut-
down when approximately
two minutes (by default) of
battery operated run time
remains.

Brightly lit: Low battery
warning interval is about
two minutes.
Dimly lit: Low battery
warning interval is about
five minutes.
Off: Low battery
warning interval is about
eight minutes.

Possible interval settings:
5, 7, 10, 12, 15, 18 min-
utes.

The low battery warning
beeps are continuous when
two minutes of run time re-
main.

You can change the warning
interval default setting
through PowerChute soft-
ware.

Synchronized Turn-on
Delay

0 seconds

20, 60, 120, 240, 480,
720, 960 seconds

The UPS will wait the speci-
fied time after the return of
utility power before turn-on
(to avoid branch circuit over-
load).

High Transfer Point

100V:
108VAC

120V:
127VAC

230V:
253VAC

100V:
110, 112, 114VAC

120V:
130, 133, 136VAC

230V:
257, 261, 265VAC

To avoid unnecessary battery
usage, set the high transfer
point higher if the utility volt-
age is chronically high and
the connected equipment is
known to work under this
condition.

Low Transfer Point

100V:
92VAC

120V:
106VAC

230V:
208VAC

100V:
86, 88, 90VAC

120V:
97, 100, 103VAC

230V:
196, 200, 204VAC

Set the low transfer point
lower if the utility voltage is
chronically low and the con-
nected equipment can tolerate
this condition.