Table 52-1. bacnet variable list – Armstrong World Industries 6100 User Manual
Page 52

52
Table 52-1. BACnet Variable List
BACnet data type
address
description
Value / (unit)
attribute
1
Fill valve status
0:off 1:on
2
Drain valve status
0:off 1:on
3
contactor 1 status
0:off 1:on
4
contactor 2 status
0:off 1:on
5
contactor 3 status
0:off 1:on
6
contactor 4 status
0:off 1:on
8
Network control
0:Local 1:Remote
1
comm type
0:485 1:PSP
2
Sensor select
0:Humidistat 1:RH sensor
3
High limit sensor select
0:not use 1:use
4
Outside temperature
0:not use 1:use
5
Network enable
0:disable 1:enable
6
Modulating Fill enable
0:enable 1:disable
1
Desired RH / Demand
(%)
2
Steam Output
(kg/hr)
3
Water level
0:low 1:normal 2:high 3:exception
4
Run status
0:Idle 1:Steam gen. 2:Cycle drain 3:End of season drain 4:Bed dring 5:Failure 6:Drain 7:heat 8:Manual drain
9:Fill 10: Test 11: Manual stop 12: Empty drain
5
Bed life
(hours)
6
Bed life
(Minutes)
7
Run Time
(hours)
8
Run Time
(Minutes)
9
Drain Freq
(hours)
10
Drain Freq
(Minutes)
11
Idle Time
(hours)
12
Idle Time
(Minutes)
13
RH / Demand (Analog input)
(%)
14
Duct value
(%)
15
Outside temperature
(
℃)
16
Water temperature
(
℃)
17
Heat temperature
(
℃)
18
Failure
1:Over temperature 2:High humidity/sail switch circuit is open 3:Illegal level switch state 4:Unit have reached
100% of bed life 5:Fill time out to low level 6:Water level dropped below level during normal run 7:Fill time
out from low to high level
19
Contactor number
1,2,3,4
20
Heating Element Power
0:1000W 1:3000 2:5000W 3:6650W 4:8000W
1
Language Select
0:English 1:Chinese
2
Set RH / Demand
(%)
3
Duct High Limit set point
(%)
4
Outside temp. high set point
(
℃)
5
Outside temp. low set point
(
℃)
6
Outside RH low set point
(%)
7
Run mode
0:Steam Gen 1:Manual Drain 2:Manual Fill 3:Unit stop
8
AQUASTAT
(
℃)
9
Bed Life
0:500hours 1:750hours 2:1000hours 3:1250hours 4:1500hours 5:1750hours 6:2000hours 7:2250hours
8:2500hours 9:3000hours 10:No bed
10
Drain Cycle
0:6hours 1:12hours 2:24hours 3:48hours 4:96hours 5:Real time drain
11
Drain duration
0:1Minutes 1:5Minutes 2:10Minutes
12
Signal type
0:0-10V 1:0-5V 2:1.9-3.9V 3:4-20mA
13
PID_DIV
14
PID_PB
15
PID_SI
(second)
16
PID_DG
17
Modulating Fill Cycle
(second)
18
Modulating Fill duration
(second)
19
Water temp. compensate
(
℃)
20
Themocouple compensate
(
℃)
analog ouput
BACNet variants list
binary input
binary output
Analog input
read only
read / write
read only
read / write