Table 51-1 Modbus Variable Lists
address description
Value / (unit)
function number Data Class
10001
Fill valve status
0:off 1:on
10002
Drain valve status
0:off 1:on
10003
contactor 1 status
0:off 1:on
10004
contactor 2 status
0:off 1:on
10005
contactor 3 status
0:off 1:on
10006
contactor 4 status
0:off 1:on
10008
Network control
0:Local 1:Remote
1
comm type
0:485 1:PSP
2
Sensor select
0:Humidistat 1:RH sensor
3
High limit sensor select
0:not use 1:use
4
Outside temperature
0:not use 1:use
5
Network enable
0:disable 1:enable
6
Modulating Fill enable
0:enable 1:disable
30001
Desired RH / Demand
(%)
30002
Steam Output
(kg/hr)
30003
Water level
0:low 1:normal 2:high 3:exception
30004
Run status
0:Idle 1:Steam gen. 2:Cycle drain 3:End of season drain 4:Bed dring 5:Failure 6:Drain 7:heat
8:Manual drain 9:Fill 10: Test 11: Manual stop 12: Empty drain
30005
Bed life
(hours)
30006
Bed life
(Minutes)
30007
Run Time
(hours)
30008
Run Time
(Minutes)
30009
Drain Freq
(hours)
30010
Drain Freq
(Minutes)
30011
Idle Time
(hours)
30012
Idle Time
(Minutes)
30013
RH / Demand (Analog input)
(%)
30014
Duct value
(%)
30015
Outside temperature
(
℃)
30016
Water temperature
(
℃)
30017
Heat temperature
(
℃)
30018
Failure
1:Over temperature 2:High humidity/sail switch circuit is open 3:Illegal level switch state 4:Unit
have reached 100% of bed life 5:Fill time out to low level 6:Water level dropped below level
during normal run 7:Fill time out from low to high level 8:Water level above high level time out
9:Water level has not dropped below low level during an emptydrain 10:End of bed dring
30019
Contactor number
1,2,3,4
30020
Heating Element Power
0:1000W 1:3000 2:5000W 3:6650W 4:8000W
40001
Language Select
0:English 1:Chinese
40002
Set RH / Demand
(%)
40003
Duct High Limit set point
(%)
40004
Outside temp. high set point
(
℃)
40005
Outside temp. low set point
(
℃)
40006
Outside RH low set point
(%)
40007
Run mode
0:Steam Gen 1:Manual Drain 2:Manual Fill 3:Unit stop
40008
AQUASTAT
(
℃)
40009
Bed Life
0:500hours 1:750hours 2:1000hours 3:1250hours 4:1500hours 5:1750hours 6:2000hours
7:2250hours 8:2500hours 9:3000hours 10:No bed
40010
Drain Cycle
0:6hours 1:12hours 2:24hours 3:48hours 4:96hours 5:Real time drain
40011
Drain duration
0:1Minutes 1:5Minutes 2:10Minutes
40012
Signal type
0:0-10V 1:0-5V 2:1.9-3.9V 3:4-20mA
40013
PID_DIV
40014
PID_PB
40015
PID_SI
(second)
40016
PID_DG
40017
Modulating Fill Cycle
(second)
40018
Modulating Fill duration
(second)
40019
Water temp. compensate
(
℃)
40020
Themocouple compensate
(
℃)
40021
First run
40022
Idle time
(hour) test for End of seanson drain
40023
Drain time
(hour) test for Cycle drain
40024
Bed life
(hour) test for End of Life
40025
Bed drying time
(hour) test for whole Bed drying cycles, 96 hours max.
40026
Bed drying time
(minute) test for one Bed Drying cycle, 30 minutes max.
Modbus Variants list
BI
Bits
AI
AV
function 2 , read
only
function 1,read only
: function 5,15
write
function4 , read
only
function3 read
only,function 6,16
write
function 6 , for
debug only
AV