beautypg.com

Armstrong World Industries 6100 User Manual

Page 43

background image

43

PID Control

PID control is essential on the HumidiClean series for maintaining the desired relative humidity (RH)

by adjusting the humidifiers output. Please note that the PID control is only used when a RH sensor is

supplying the demand in place of a humidistat (configured in Operation Setup Menu). The PID Settings

will control how the demand is adjusted according to the error between the current RH and the desired

RH set point. There are four variables of the PID control that can be adjusted to customize the way

your HumidiClean reacts to a demand signal.

Proportional Band (PB) – The proportional band value determines how your humidifier will react to

the current error (desired – current). Smaller PB values will take longer for your unit to reach its RH set

point. Larger PB values will quickly reach their RH set points but possibly result in demand instability

(demand bounces between on and off). The default PB value on the HumidiClean is 15.

Integral Reset Value (IRV) – The integral reset value determines how your humidifier will react to the

sum of the amount of error in the past. By decreasing the IRV, you will have less overshoot after you

reach your RH set point, but increase the amount of time it takes to reach the set point. Increasing

your IRV will allow you to quickly achieve your RH set point and reach a steady demand, but will have

higher RH overshoot in the process. The default IRV value on the HumidiClean is 125.

Derivative Gain (DG) – The derivative gain value determines how much your demand will be affected

by the past rate of change of error on your HumidiClean. Larger DG values will improve the demand

stability and decrease RH overshoot near the RH set point. However, larger DG values can also

amplify any noise in the demand signal between the controller and the HumidiClean, giving the unit an

unstable demand. The default DG value on the HumidiClean is 0.

SI Interval (SI) – The SI interval value controls how much data from the past is used for calculating

the integral term and derivative term. The SI interval value is in seconds, so the default SI integral

value of 10 means 10 seconds of past error data is used when calculating the integral and derivative

terms.

Shortcuts to tuning your PID values – If your HumidiClean:

-

is not reaching its desired RH quick enough, increase the proportional band (PB) value or

integral reset value (IRV) slowly until acceptable rate is reached. Increasing both of these values

will help you reach your desired RH value quicker. Caution, increasing your PB value too high can

create an unstable demand scenario when your demand will bounce between having a demand

and zero, causing your contactor to pull in and out constantly. Avoid this by slowly increasing your

PB value in increments as to not raise it too high. Increasing your IRV value too high will result

in higher overshoot, causing your %RH to rise above the desired %RH (higher IRV values create

higher overshoot).

-

has too high of an overshoot, decrease the integral reset value (IRV) or increase the derivative

gain (DG) slowly until acceptable overshoot is found. Decreasing the IRV will decrease your

overshoot, but it will also increase the time it takes for your humidifier to reach its desired RH.

Increasing your DG value will help improve demand stability (reaching a constant demand value)

and decrease set point overshoot, but could amplify any signal noise (if there is any) coming from

your RH sensor. Amplifying signal noise could create an unstable demand and create a false

demand (humidifying when there is no need).

This manual is related to the following products: