PULS ML50.100 User Manual
Page 3
ML50 Instruction Manual Power Supplies
ML50 Bedienungsanleitung für Stromversorgung
Technical Data
1)
Technische
Daten
1)
ML50.100
ML50.109
14)
ML50.101
ML50.111
15)
ML50.102
ML50.105
Output Voltage
Ausgangsspannung
nom.
DC 24-28V
DC 24-28V
DC 12-15V
17
)
DC 48-56V
Factory Setting at Full Load
Werkseinstellung bei Nennlast
typ.
24.5V 24.0V
16
) 15.0V
17
)
48.0V
Output Current
Ausgangsstrom
nom.
2.1A at 24V
1.8A at 28V
2.1A at 24V
1.8A at 28V
4.2A at 12V
3.3A at 15V
1.05A at 48V
0.9A at 56V
Output Power
Ausgangsleistung
nom.
50W
50W 50W
50W
Output Ripple & Noise Voltage
2)
Ausgangswelligkeit
2
)
max.
50mVpp
50mVpp 50mVpp
50mVpp
AC Input Voltage
AC Eingangsspannung
nom.
AC 100-240V
-15%/+10%
AC 100-240V
-15%/+10%
AC 100-240V
-15%/+10%
AC 100-240V
-15%/+10%
Input Frequency
Eingangsfrequenz
nom.
50-60Hz
50-60Hz 50-60Hz
50-60Hz
AC Input Current
3)
AC
Eingangsstrom
3)
typ.
0.83A / 0.52A
0.83A / 0.52A
0.83A / 0.52A
0.83A / 0.52A
Power Factor
3)
Leistungsfaktor
3)
typ.
0.56 / 0.48
0.56 / 0.48
0.56 / 0.48
0.56 / 0.48
Allowed Voltage L or N to Earth
Erlaubte Spannung L oder N zu Erde
max.
264Vac / 375Vdc
264Vac / 375Vdc
264Vac / 375Vdc
264Vac / 375Vdc
DC Input Voltage
13)
DC
Eingangsspannung
13)
nom.
DC 110-300V
-20%/+25%
DC 110-300V
-20%/+25%
DC 110-300V
-20%/+25%
DC 110-300V
-20%/+25%
Input Inrush Current
4)
Einschaltspitzenstrom
4)
typ.
17A / 35A
17A / 35A
17A / 35A
17A / 35A
Hold-up Time
3)
Pufferzeit
3)
typ.
40ms / 180ms
40ms / 180ms
40ms / 180ms
40ms / 180ms
Efficiency
3)
Wirkungsgrad
3)
typ.
88.4% / 89.0%
88.4% / 89.0%
89.4% / 90.5%
89.7% / 90.5%
Power Losses
3)
Verlustleistung
3)
typ.
6.6W / 6.2W
6.6W / 6.2W
6.1W / 5.3W
6.2W / 5.3W
Operational Temperature Range Betriebstemperaturbereich
nom.
-10°C - +70°C
-10°C - +70°C
-10°C - +70°C
-10°C - +70°C
Output Derating
Leistungsrücknahme
+60°C to +70°C
1.3W/°C
1.3W/°C
1.3W/°C
1.3W/°C
Storage Temperature Range
Lagertemperaturbereich
nom.
-40°C - +85°C
-40°C - +85°C
-40°C - +85°C
-40°C - +85°C
Humidity
5)
Feuchte
5)
IEC 60068-2-30
5 - 95% r.H.
5 – 95% r.H.
5 - 95% r.H.
5 - 95% r.H.
Vibration Schwingen
IEC 60068-2-6
2g
2g
2g
2g
Shock Schocken
IEC 60068-2-27
15g 6ms, 10g 11ms
15g 6ms, 10g 11ms
15g 6ms, 10g 11ms
15g 6ms, 10g 11ms
Degree of Pollution (non-conductive) Verschmutzungsgrad
(nicht leitend)
EN 50178, IEC 62103
2
2
2
2
Degree of Protection
Schutzart
EN 60529
IP20
IP20
IP20
IP20
Class of Protection
Schutzklasse
IEC 61140
I
6)
I
6)
I
6)
I
6)
Over-temperature Protection
Übertemperaturschutz
OTP
No / Nein
No / Nein
No / Nein
No / Nein
Output Over-voltage Protection Überspannungsschutz
am
Ausgang
OVP, max.
40Vdc
40Vdc
20Vdc
60Vdc
Leakage Current
7)
TN/TT-mains PE-
Ableitstrom
7)
TN/TT- Netze
max.
0.23mA / 0.40mA
0.23mA / 0.40mA
0.23mA / 0.40mA
0.23mA / 0.40mA
IT-mains
IT- Netze
0.49mA / 0.81mA
0.49mA / 0.81mA
0.49mA / 0.81mA
0.49mA / 0.81mA
Return Voltage Resistance
8)
Rückspeisefestigkeit
8)
max.
35Vdc
35Vdc 22Vdc
63V
Parallel Use
11)
Parallelschaltbar
11)
-
Yes / Ja
Yes / Ja
Yes / Ja
Yes / Ja
Serial Use
12)
Serienschaltbar
12)
-
Yes / Ja
Yes / Ja
No / Nein
Yes / Ja
Dimensions
9)
(WxHxD) Abmessungen
9)
(BxHxT)
nom.
45x75x91mm
45x75x91mm 45x75x91mm
45x75x91mm
Weight Gewicht
max.
240g / 0.53lb
240g / 0.53lb
240g / 0.53lb
240g / 0.53lb
DC-OK Signal
DC-OK Signal
Yes / Ja
Yes / Ja
No / Nein
No / Nein
1) All parameters are specified at 230Vac input voltage, TN- TT- IT-mains, nominal output
current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
2) 50-Ohm measurement, bandwidth 20MHz
3) at 120Vac, 60Hz / 230Vac 50Hz
4) Peak value at 120Vac / 230Vac, at an ambient temperature of 40°C and cold start.
5) Do not energize while condensation is present.
6) PE connection required (Ground).
7) Leakage current at 132Vac, 60Hz / 264Vac, 50Hz
8) Loads such as decelerating motors and inductors can feed voltage back to the output of the
power supply. The figure represents the maximum allowed feed back voltage
9) Depth without DIN-rail.
11) ML50.101, ML50.111: These units are optimized for parallel operation and are equipped with
the “Parallel Use” feature. The units can be used in parallel over the entire temperature range.
ML50.100, ML50.102, ML50.105, ML50.109: These units are equipped with the standard
“Single Use” output characteristic. There is no current share between the units, make sure
that the ambient temperature stays below 45°C.
A fuse or diode on the output of each unit is required if more than three units are connected in
parallel.
12) Use only power supplies of the same type. The total output voltage should not be >150Vdc.
13) Use a battery or a similar DC source. Connect +pole to L and –pole to N. A supply from the
intermediate DC-bus of a frequency converter is not recommended and can cause a
malfunction or damage the unit. Additional tests might be necessary during the approval
process of a complete system.
14) Version with conformal coated PC-board
15) Version with pluggable screw terminals, depth of unit: 98mm
16) The ML50.101 and ML50.111 are optimized for parallel operation and are equipped with the
“Parallel Use” feature. This feature regulates the output voltage in such a manner that the
voltage at no load is approx. 5% higher than at nominal load.
17) The output voltage range can be set by a jumper (link between pin 4 and 5 of the output
terminals). The output voltage will be 15V when the connection is installed. The voltage will
jump to 12V when removing this connection and then can be adjusted up to 15V.
1) Alle Werte gelten bei 230Vac, TN- TT- IT-Netze, Nennausgangsstrom, 25°C Umgebung und
nach einer Aufwärmzeit von 5 Minuten, wenn nichts anderes angegeben ist.
2) 50-Ohm Messung, Bandbreite 20MHz
3) bei 120Vac, 60Hz / 230Vac, 50Hz
4) Spitzenstrom bei 120Vac / 230Vac, einer Umgebungstemperatur von 40°C und Kaltstart.
5) Nicht betreiben, solange das Gerät Kondensation aufweist.
6) PE Verbindung erforderlich.
7) Ableitstrom bei 132Vac, 60Hz / 264Vac, 50Hz
8) Bremsende Motoren oder Induktivitäten können Spannung zum Ausgang des Netzteils
rückspeisen. Der Wert gibt die max. zulässige Rückspeisespannung an.
9) Tiefe ohne DIN-Schiene
11) ML50.101, ML50.111: Diese Geräte sind für den Parallelbetrieb optimiert und mit dem
“Parallel Use” Feature ausgestattet. Ein Parallelbetrieb ist für den gesamten
Temperaturbereich erlaubt.
ML50.100, ML50.102, ML50.105, ML50.109: Diese Geräte sind mit die standardmäßige
“Single Use” Ausgangscharakteristik ausgestattet. Keine Stromaufteilung zwischen den
Geräten. Erlaubt bis max. 45°C Umgebungstemperatur.
Eine Sicherung oder Diode je Ausgang ist erforderlich wenn mehr als 3 Geräte parallel
geschaltet werden.
12) Nur gleiche Geräte bis zu einer Gesamtspannung von 150Vdc
13) Geeignet sind Batterien oder ähnliche Quellen. Den +Pol an L und –Pol an N anschließen.
Ein Betrieb am Zwischenkreis von Frequenzumrichtern wird nicht empfohlen und kann zu
Defekten oder Fehlfunktionen führen. Bei Zulassung eines Gesamtsystems können zusätzlich
Prüfungen erforderlich werden.
14) Version mit schutzlackierte Leiterplatte
15) Version mit steckbaren Schraubklemmen, Gesamttiefe 98 mm
16) Die ML50.101 und ML50.111 sind für den Parallelbetrieb optimiert und fest auf den Modus
„Parallel Use“ eingestellt. Dieser Modus regelt die Ausgangsspannung so, dass diese im
Leerlauf um etwa 5% höher ist als bei Nennlast.
17) Die Ausgangsspannungsbereich kann mittels eines Jumpers (Verbindung zwischen Pin 4 und
5 der Ausgangsklemme gewählt werden. Bei installierter Verbindung ist die Spannung 15V.
Bei Entfernung der Brücke geht die Spannung auf 12V und lässt sich dann mit dem
Potentiometer bis 15V einstellen.