Calibration

Board Cover

Printed Circuit

Storage Position

Calibration Tool in

Ready to Press

Calibration Switch

Switch

Calibration Tool

in Access Hole

W E I G H T =

X X . X

L B

A U T O M A T I C

?

5

>>>>>

ENTER

W E I G H T =

X X . X

L B

S E T U P

?

5

Press Calibration Switch

W E I G H T =

X X . X

L B

C H A R G I N G

>

O V E R

C H A R G E

A M O U N T =

X . X X

K G

5

><

ENTER

SET OVER CHARGE AMOUNT

1. Remove two screws on each side to remove front cover. Remove four

screws and carefully tilt top control panel up to gain access to printed
circuit board cover.

2. Turn the Main Power Switch on.

Refer to the figure below to locate the access hole for the Calibration
Switch which is on the underside of the Circuit Board Cover.

3. Remove the plastic Calibration Tool.

4. Press the

>

key five times to display WEIGHT= XX.X LB SETUP? 5 .

5. Gently press the Calibration Switch with the Calibration Tool.

The Display will read WEIGHT= XX.X LB CHARGING.

6. Press the

>

key. The Display will read OVER CHARGE AMOUNT= X.XX

KG5.

7. Press the

>

key to change the value of the field. Press the

<

key to move

to a different field. The value entered will be stored until this procedure is
run again and a new value is entered. Press the ENTER key to accept the
value. The Display will then return to the Main Menu.

1 oz = 0.02835 Kg 1 Lb = 0.45359 Kg

8. Place the Calibration Tool in the storage hole.

9. Lower top control panel, being careful to not bend or crimp copper tubes,

and install screws. Replace the front cover.

Calibration Tool Part No. 360-81214-00