Table 1 - Performance and Dimensional Data - Tubular Blower Unit Heater

Unit

Size

100 125 150 175 200 250

300 350 400

PERFORMANCE DATA†
Input

-

BTU/Hr.

100,000 125,000 150,000 175,000 200,000 250,000

300,000 350,000 400,000

(kW)

(29.3) (36.6) (44.0) (51.3) (58.6) (73.3)

(87.9) (102.6)

(117.2)

Output

-

BTU/Hr.

83,000 103,750 124,500 145,250 166,000 207,500

246,000 290,500 332,000

(kW)

(24.3) (30.4) (36.5) (42.6) (48.6) (60.8)

(72.1) (85.1) (97.3)

Thermal Effi

ciency

-

%

83 83 83 83 83 83

82 83 83

Free Air Delivery - CFM

1,181

1,476

1,771

2,067

2,362

2,953

3,501

4,134

4,724

(cu.

m/s)

(0.557) (0.697) (0.836) (0.976) (1.115) (1.394)

(1.652) (1.951) (2.230)

Air

Temperature

Rise

-

Deg.

F

65 65 65 65 65 65

65 65 65

(Deg.

C)

(36) (36) (36) (36) (36) (36)

(36) (36) (36)

Outlet

Velocity

-

FPM

370 463 555 395.0

451.0

564.0 422 498 570

(m/s)

(1.879) (2.351) (2.819) (2.006) (2.291) (2.864)

(2.143) (2.529) (2.895)

Full Load Amps at 115V

7.3

9.4

9.4

14.2

14.2

15.6

15.6

20.8

20.8

Maximum

Circuit

Ampacity

8.6 11.2 11.2 17.1 17.1 18.9

18.9 25.4 25.4

MOTOR DATA: Motor HP

1/4

1/2

1/2

3/4

3/4

1

1

1-1/2

1-1/2

Motor kW

0.19

0.37

0.37

0.56

0.56

0.75

0.75

1.11

1.11

Motor Type ODP**

SPH

SPH

SPH

SPH

SPH

Cap. Start

Cap. Start

Cap. Start

Cap. Start

RPM

1,725

1,725

1,725

1,725

1,725

1,725

1,725

1,725

1,725

Amps @ 115V

5.1

7.2

7.2

11.6

11.6

13.0

13.0

18.2

18.2

DIMENSIONAL DATA - inches (mm)

"A"

Height

to

Top

of

Flue

33-3/4 33-3/4 33-3/4 33-3/4 33-3/4 33-3/4

34

34

34

(857) (857) (857) (857) (857) (857)

(864) (864) (864)

"B"

Jacket

Width

of

Unit

20-3/4 20-3/4 20-3/4 32-3/4 32-3/4 32-3/4

50-3/4 50-3/4 50-3/4

(527) (527) (527) (832) (832) (832)

(1289)

(1289)

(1289)

"C"

Width

to

Centerline

Flue 13-3/8 13-3/8 13-3/8 19-3/8 19-3/8 19-3/8

28-3/8 28-3/8 28-3/8

(340) (340) (340) (492) (492) (492)

(721) (721) (721)

"D"

Depth

to

Front

Hanger 21 21 21 21 21 21

21 21 21

(533) (533) (533) (533) (533) (533)

(533) (533) (533)

"E"

Hanging

Distance

Width 18-5/8 18-5/8 18-5/8 30-5/8 30-5/8 30-5/8

48-5/8 48-5/8 48-5/8

(473) (473) (473) (778) (778) (778)

(1235)

(1235)

(1235)

"F"

Hanging

Distance

Depth

19 19-1/2 19-1/2 32-3/4 32-3/4 32-3/4

23-1/2 32-3/4 32-3/4

(483) (495) (495) (832) (832) (832)

(597) (832) (832)

"G"

Discharge

Opening

Width 18-3/4 18-3/4 18-3/4 30-3/4 30-3/4 30-3/4

48-3/4 48-3/4 48-3/4

(476) (476) (476) (781) (781) (781)

(1238)

(1238)

(1238)

"H"

Depth

to

Centerline

Flue 4-3/4 4-3/4 4-3/4 4-3/4 4-3/4 4-3/4

5-1/8 5-1/8 5-1/8

(121) (121) (121) (121) (121) (121)

(130) (130) (130)

"L"

Discharge

Opening

Height 24-1/2 24-1/2 24-1/2 24-1/2 24-1/2 24-1/2

24-1/2 24-1/2 24-1/2

(622) (622) (622) (622) (622) (622)

(622) (622) (622)

"M"

Overall

Unit

Width

25-1/4 25-1/4 25-1/4 37-1/4 37-1/4 37-1/4

55-1/4 55-1/4 55-1/4

(641) (641) (641) (946) (946) (946)

(1403)

(1403)

(1403)

"P"

Overall

Unit

Depth

49-3/4 49-3/8 49-3/8 56-1/8 56-1/8 56-1/8

53-3/8 56-1/8 56-1/8

(1264) (1254) (1254) (1426) (1426) (1426)

(1356) (1426) (1426)

*Flue

Size

Diameter

-

in

5 5 5 5 5 5

6 6 6

(mm)

(127) (127) (127) (127) (127) (127)

(152) (152) (152)

Blower Size - inches (Qty)

9

10

10

12

12

12

10 (2)

12 (2)

12 (2)

Gas Inlet, Natural Gas - in

1/2

1/2

1/2

1/2

1/2

3/4

3/4

3/4

3/4

Gas Inlet, LP Gas - in

1/2

1/2

1/2

1/2

1/2

1/2 OR 3/4

1/2 OR 3/4

1/2 OR 3/4

1/2 OR 3/4

Approximate

Unit

Weight

-

lb 171 175 202 245 264 289

370 390 429

(kg)

(78) (79) (92) (111) (120) (131)

(168) (177) (195)

Approximate

Ship

Weight

-

lb 256 261 289 381 400 425

520 547 595

(kg)

(116) (118) (131) (173) (181) (193)

(236) (248) (270)

† Ratings shown are for unit installations at elevations between 0 and 2,000 ft (0 to 610m). For unit installations in U.S.A. above 2,000 ft. (610m), the unit input must be fi eld derated 4%

for each 1,000 ft. (305m) above sea level; refer to local codes, or in absence of local codes, refer to the latest edition of the National Fuel Gas Code, ANSI Standard Z223.1 (N.F.P.A. No. 54).

For installations in Canada, any reference to deration at altitudes in excess of 2,000 ft. (610m) are to be ignored. At altitudes of 2,000 ft. to 4,500 ft. (610 to 1372m), the unit must be

fi eld derated to 90% of the normal altitude rating, and be so marked in accordance with the ETL certifi cation. See Table 8A for fi eld deration information.

* Flue collar is factory supplied with unit; to be fi eld installed per included instructions.
** LEGEND:

SPH = SPLIT PHASE CAP. START = CAPACITOR START ODP = OPEN DRIP PROOF