List of parameters, Maintenance, calibration apparatus – Yokogawa JUXTA FR5V RTD Converter (Free Range Type) User Manual
Page 4: 2 calibration procedure

4
IM 77J08R05-01E 1st Edition
2007.01.15-00
5. LIST OF PARAMETERS
Parameter Display
Items
A
DISPLAY
Display
A01
INPUT
Input value
A02
OUTPUT
Output value
A03
STATUS
Status (*1)
A04
REV NO
Revision number
B
SET
Setting
B01
TAG NO.1
Tag number 1
B02
TAG NO.2
Tag number 2
B03
COMMENT1
Comment 1
B04
COMMENT2
Comment 2
B05
TYPE
Input type
B09
UNIT
Unit
B10
ZERO
Zero (0% of input range)
B11
SPAN
Span (Input span)
B12
BURN OUT
Burnout
C
ADJUST
Adjustment
C01 OUT 0%
Output 0% adjustment
C02 OUT 100%
Output 100% adjustment
C04 ZERO ADJ
Input zero adjustment
C05 SPAN ADJ
Input span adjustment
*1: This “STATUS” is for the customer’s engineer to check the history.
6. MAINTENANCE
The product starts running immediately when the power is turned
on; however, it needs 10 to 15 minutes of warm-up before it
meets the specified performance.
6. Calibration Apparatus
A 6-dial variable resistor (Yokogawa Meters & Instruments
Corporation 279301 or equivalent)
A digital multimeter (Yokogawa 7561 or equivalent)
A precision resistor of 250 Ω ±0.01%, 1W
A setting tool for adjustment (Refer to "4. Setting Parameters"
in this manual.
6.2 Calibration Procedure
1. Connect the instruments as shown below.
1
2
3
4
5
6
7
3
2
6
7
4
5
1
A
B
B
6-dial
variable resistor
Setting tool
Output
Input
24V DC
Ro
Ro: 250Ω precision resistor for
current output
DMM
Power Supply
2 Use the 6-dial variable resistor and apply the resistance
equivalent to 0, 25, 50, 75, and 100% of the measuring range
to the converter.
3. Verify that the corresponding output voltages are 0, 25, 50, 75,
and 100% respectively and within the specified accuracy rating.
(R
o
is used for current output.)
Use the setting tool (VJ77 Parameter Setting Tool or JHT200
Handy Terminal) to adjust the input/output signals.
Input Adjustment Procedure
(1)
Input the value equivalent to 0% value of the input range
to the converter.
(2)
Read the parameter
[C04: ZERO ADJ] and check the
input value.
(3)
Select “INC” or “DEC” in the parameter
[C04: ZERO
ADJ] to adjust.
INC: Increase (Adjusts the increased value of the input
[resistance] value)
DEC: Decrease (Adjusts the decreased value of the
input [resistance] value)
RST: Reset of the adjustment value
(4)
Input the value equivalent to 100% value of the input
range to the converter.
(5)
Read the parameter
[C05: SPAN ADJ] and check the
input value.
(6)
Adjust the span in the same way as (3).
Output Adjustment Procedure
When adjusting 0% value of output:
(1) Set the adjustment value 0% in the parameter
[C0:
OUT 0%].
•The value equivalent to 0% of the output range will be
output, irrespective of the input.
(2) Check the output value via digital multimeter, and adjust
it in the parameter
[C0: OUT 0%].
•If it slips out to the (+) side, set (−) value equivalent
to slipout; if it slips out to the (−) side, set (+) value
equivalent to slipout for adjusting the output value to
0%.
*: The 100% value of output can be adjusted by the
same operation as the above in [C02:OUT100%]
For adjustment using a setting tool, refer to the User’s Manual for
each setting tool and “5. List of Parameters” in this manual.
User’s Manual for VJ77 [Document No.: IM 77J01J77-01E];
however, use the VJ77 of version R1.05 or later.
User’s Manual for JHT200 [Document No.: IM JF81-02E]