Setting parameters – Yokogawa JUXTA FR5V RTD Converter (Free Range Type) User Manual
Page 3

3
IM 77J08R05-01E 1st Edition
2007.01.15-00
M4 screw terminals are provided for the connection of external
signals. Attach a crimp-on lug to each wire for connection to the
terminals.
●Recommended cables: A nominal cross-sectional area of 0.5
mm
2
or thicker for signal cables, and that of 1.25 mm
2
or thicker
for power cables.
Wiring Diagram
1
2
3
4
5
6
7
3
2
6
7
4
5
1
A
+
−
Input (RTD)
Output
Power Supply
B
B
+
−
NOTE
●The power line and input/output signal lines should
be installed away from noise-generating sources.
Otherwise accuracy cannot be guaranteed.
●The wiring resistance of input terminals and
should be the same.
●Adhere strictly to the specifications to avoid
overheating or damage. Before turning on the power,
ensure the following:
(a) Power supply voltage and input signal value
applied to the product should meet the required
specifications.
(b) The external wiring to the terminals and wiring to
ground are as specifications.
●Do not operate the product in the presence of
flammable or explosive gases or vapors.
●The product is sensitive to static electricity; exercise
care when in operation. Before you operate the
product, touch a nearby metal part to discharge
static electricity.
Power Supply and Isolation
Power supply voltage: 24V DC ±10% (ripple: less than 5% p-p)
Current consumption: FR5A 65mA, FR5V 50mA
Insulation resistance: 100M Ω at 500V DC between input, output
and power supply mutually.
Withstand voltage: 1500V AC/minute between input-output,
input-power supply
500V AC/minute between output-power supply
4. SETTING PARAMETERS
The parameters are set as you specified in your order. Refer
to the following to change the default settings.
Set the parameters using a PC (VJ77 Parameter Setting Tool)
or the Handy Terminal. Refer to "5. List of Parameters" in this
manual and the User’s Manual for VJ77 PC-based Parameters
Setting Tool (IM 77J01J77-01E) or the User’s Manual for JHT200
Handy Terminal (IM JF81-02E). Parameters are shown in
brackets "[ ]".
Connection of Setting Tools
VJ77 Dedicated adapter (E9789HA)
[Provided with VJ77]
PC with VJ77 installed
Dedicated cable (E9786WK)
[Provided with VJ77]
*Be sure to use the VJ77 of version R1.05 or later.
JHT200
Handy Terminal
JUXTA communication cable
3 pin connector (F9182ED)
[Provided with VJ77 and JHT200]
Setting RTD Type
Set the RTD type to be connected to the input in
[B05: TYPE].
Display Type of input
Measuring
range
Measuring
span
PT
Pt100
(IPTS-68:JIS'89)
-200 to 660°C
10°C
or more
JPT
JPt100 (JIS'89)
-200 to 10°C
PT100-90 Pt100 (ITS-90:JIS'97) -200 to 850°C
PT50
Pt50 (JIS'81)
-200 to 649°C
JPt100 (JIS'89): R0=100Ω, R100/R0=1.3916
Pt100 (IPTS-68): R0=100Ω, R100/R0=1.3850
Pt100 (ITS-90): R0=100Ω, R100/R0=1.3851
Setting Temperature Unit
Set the temperature unit of the input range in
[B09: UNIT]
NOTE
Do not set the "-----" as the temperature unit, even if it
is displayed during the setting.
Otherwise it may cause the malfunction or damage.
Setting Input Range
Set the zero percent value of input range in
[B0: ZERO], and
the span of input range in
[B: SPAN].
Setting Burnout Action
Set the burnout action in
[B2: BURN OUT]
Set "OFF", "UP", or "DOWN."
NOTE
Input adjustment should be applied when the setting
of input range, burnout action direction or input wiring
has been changed.