Yokogawa JUXTA M Series Digital Limit Alarms MVHK User Manual
Page 8

IM 77J04H31-01E 3rd Edition : 2006.08.31-00
8
14. MAIN SPECIFICATIONS
■
Model and Suffix Codes
-
0 - 0 /
Type
Power Supply
Input Signal
Output Signal
Monitor Output
Optional Specification
-0
-1
0
3
6
-6
-A
-U
-Z
1
2
6
A
P
N
0
/R100
/R250
/SN
Digital Limit Alarm (DC Input Type)
General use type
JK12 type (The terminal assignment is same as that of Yokogawa’s JK12 and MHKW.)
Always 0
24 V DC
±
10%
100-240 V AC/DC (Operating range: 85 to 264 V AC/DC)
1 to 5 V DC
4 to 20 mA DC (with 250
Ω
receiving resistor)
DC voltage or DC current signal
Custom order
Alarm output (transfer contact [1a1b] ), 2 points
Alarm output (NO contact), 4 points
1 to 5 V DC
4 to 20 mA DC
Communication function (RS-485)
No monitor output
Always 0
With 100
Ω
receiving resistor
With 250
Ω
receiving resistor
Without socket
Model
MVHK
Suffix Codes
Description
■
Input and Display
Number of inputs: 1 point
Input signal: Set the measured input range within the instrument input range. (Refer to
Section 7.2.)
Input resistance:
For voltage input: 1 M
Ω
(100 k
Ω
during power off)
For current input: 100
Ω
or 250
Ω
(with external receiving resistor)
(Specify at the time of order.)
Input scaling (displayed value): -1999 to 9999 (Decimal point position can be set.)
PV (measured value) display: 4-digit, 7-segment, red/green LED, character height of
13.5 mm
Data display: 4-digit, 7-segment, green LED, character height of 9 mm
Alarm indicator lamp: 2 orange LEDs for 2 points of alarms or 4 orange LEDs for 4
points of alarms. Lights up if an alarm occurs.
Economical mode: Turns off the indicating LED if no keystroke is made within the set
time.
Setting range: 0 (does not go off) or 1 to 60 minutes
Active color PV display (PV display color changing function): This function changes the
PV display color from green to red or from red to green according to the set
PV display color mode shown below.
[PV display color mode to be set]
Link to alarm 1: Links to alarm 1.
Link to alarm 1 and alarm 2: Links to alarm 1 and alarm 2.
Link to alarm 1 to alarm 4 (only for 4 points of alarms): Links to alarm 1 to alarm 4.
SP deviation: Changes the PV display color according to whether measured value is
less than SP deviation high limit or SP deviation high limit or more; whether
measured value is more than SP deviation low limit or SP deviation low limit
or less.
PV limit: Changes the PV display color according to whether measured value is less
than measured range high limit or measured range high limit or more;
whether measured value is more than measured range low limit or measured
range low limit or less.
Fixed color: Fixes PV display color in green or red.
■
Output
Signal type: Relay contact
Number of outputs: 2 points of contact outputs (transfer contact [1a1b] ) or 4 points of
contact outputs (NO contact)
Contact rating: 120 V AC/1 A, 220 V AC/0.5 A (resistance load)
30 V DC/1 A, 120 V DC/0.1 A (resistance load)
Alarm action:
PV high-limit alarm
PV low-limit alarm
Deviation high-limit alarm
Deviation low-limit alarm
Deviation high and low-limit alarm
Deviation within high and low-limit alarm
Energized or de-energized under normal condition
Energized or de-energized under normal condition
Energized or de-energized under normal condition
Energized or de-energized under normal condition
De-energized under normal condition
De-energized under normal condition
Alarm action
Relay action
Alarm setting range: Within the set input scaling value
Setting resolution: 1 digit
(Note)
Setpoint setting: Virtual setpoint when the deviation alarm occurs
Setting range: Within the set input scaling value
Setting resolution: 1 digit
(Note)
Hysteresis setting range: The value resulting from adding a hysteresis value to an alarm
setpoint should be within the range of set input scaling value.
Setting resolution: 1 digit
(Note)
Note: The content of 1 digit is variable according to the input scaling value.
Alarm ON delay setting: Condition monitoring time from the establishment of alarm
conditions to its output
Setting range: 0 to 999 seconds
Setting resolution: 1 second (However, about 0.2 second is to be added to the set time
to prevent wrong operation.)
Alarm OFF delay setting: Condition monitoring time from the establishment of return-to-
normal conditions to its output
Setting range: 0 to 999 seconds
Setting resolution: 1 second (However, about 0.2 second is to be added to the set time
to prevent wrong operation.)
■
Monitor Output
●
Analog Output
Output signal: 1 to 5 V DC or 4 to 20 mA DC
Allowable load resistance: 2 k
Ω
or more for 1 to 5 V DC
350
Ω
or less for 4 to 20 mA DC
Output variable range: -6 to +106%
Output scaling: Set any value within the set input scaling value (displayed value).
Output accuracy:
±
0.1% of output span (However, the accuracy is limited in the
following cases according to the scaling setting.)
When the input range corresponding to the output scaling is less than 5 V in the
instrument input range H:
Accuracy =
±
0.1 (%)
ϫ
5 (V)
Corresponding input range (V)
(%)
When the input range corresponding to the output scaling is less than 2.5 V in the
instrument input range M:
Accuracy =
±
0.1 (%)
ϫ
2.5 (V)
Corresponding input range (V)
(%)
When the input range corresponding to the output scaling is less than 0.5 V in the
instrument input range L:
Accuracy =
±
0.1 (%)
ϫ
0.5 (V)
Corresponding input range (V)
(%)
For current input, apply the value [input range
ϫ
input resistance] to the above, and
add the resistor error 0.1%.
●
Communication Output (RS-485)
The MVHK can be connected to a personal computer, graphic panel, Yokogawa’s
programmable controller FA-M3 or programmable controllers of other manufacturers.
Standards: EIA RS-485
Maximum number of connectable units: 31 units
Maximum communication distance: 1200 m
Communication method: 2-wire half duplex, start-stop synchronization, non-procedural
Baud rate: 1200, 2400, 4800 or 9600 bps
Data length: 8 or 7 bits
Stop bit: 1 or 2 bits
Parity: Even, odd or none
Communication protocol: PC link, PC link with SUM, MODBUS ASCII, MODBUS RTU or
Ladder
PC link communication: Communication protocol with a personal computer, graphic
panel or UT link module of FA-M3
MODBUS communication: Communication protocol with a personal computer
(SCADA).
Ladder communication: Communication protocol with ladder communication module of
FA-M3 and programmable controller of other manufacturers.
■
Standard Performance
Input display accuracy:
±
0.1%
±
1 digit of instrument input range span
Alarm action point setting accuracy:
±
0.1%
±
1 digit of instrument input range span
For current input, add the resistor error 0.1%.
Response speed: 500 ms (Time to alarm output when the input change is 10 to 90% and
alarm setpoint is 50%. When the alarm delay setting and hysteresis are
minimum.)
Insulation resistance: 100 M
Ω
/500 V DC between inputs, alarm outputs, power supply
and monitor output mutually.
Withstand voltage: 2000 V AC/minute between inputs, (alarm outputs 1, 2, 3 and 4),
monitor output and power supply mutually.
However, the following is excluded.
1000 V AC/minute between (alarm outputs 1 and 4) and (alarm outputs 2 and
3) and between inputs and monitor output.
(For 2 points of alarms, alarm outputs 3 and 4 are excluded.)
Power supply voltage: 24 V DC
±
10%, 100-240 V AC/DC (-15%, +10%) 50/60Hz
Power consumption: 24 V DC 3.0 W, 110 V DC 2.4 W, 100 V AC 3.9 VA,
200 V AC 5.3 VA
Effect of power supply fluctuation:
±
0.1% of span or less for the fluctuations within the
allowable range of each power supply specification
Effect of ambient temperature change:
±
0.2% of span or less for a temperature change
of 10
°
C
■
Mounting, Appearance and Environmental Conditions
Construction: Plug-in type
Material:
Casing; ABS resin (black), UL94 V-0
Socket; Modified polyphenylene oxide resin, including glass fiber (black),
UL94-V1
Mounting method: Wall or DIN rail mounting
Connection method: M3.5 screw terminal for input/output and power supply
3-pin 2-piece connector for monitor output
External dimensions: 51(W)
ϫ
86.5(H)
ϫ
133(D) mm (including a socket)
Weight:
Main unit; approx. 270 g
Socket; approx. 80 g
Operating temperature range: 0 to 50
°
C
Operating humidity range: 5 to 90% RH (no condensation)
Operating conditions: Avoid installation in such environments as corrosive gas like
sulfide hydrogen, dust, sea breeze and direct sunlight.
■
External Dimensions
103
133
50
*1 To be added when the monitor output is specified.
Monitor output
terminal *1
10
30
3.3
7.8
2-Ø4.5
Mounting hole
(depth: 24.5)
DIN rail
40
35.4
81
80
86.5
85
(25)
Main unit
Socket
51 max.
11-M3.5
ϫ
7
screw
Receiving resistor
Unit: mm