Yokogawa JUXTA MU5D User Manual
User’s manual, Checking product specifications and packaged items, General

User’s
Manual
Network Solutions Business Division
2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 Japan
Phone: +81-422-52-7179
Facsimile: +81-422-52-6619
1
Please read through this User’s Manual before use for correct handling.
Please keep this User’s Manual for future reference.
Model MU5D
Universal Temperature
Converter
(2-output, Free Range Type)
CAUTIONARY NOTES FOR SAFE USE
OF THE PRODUCT
This User’s Manual should be carefully read before installing and oper-
ating the product. The following symbol is used on the product and in
this manual to ensure safe use.
This symbol is displayed on the product when it is
necessary to refer to the User’s Manual for information on
personnel and instrument safety. This symbol is displayed
in the User’s Manual to indicate precautions for avoiding
danger to the operator, such as an electric shock.
The following symbols are used only in this manual.
IMPORTANT
Indicates that operating the hardware or software in a
particular manner may cause damage or result in a system
failure.
NOTE
Draws attention to essential information for understanding
the operations and/or functions of the product.
CHECKING PRODUCT SPECIFICATIONS AND PACKAGED ITEMS
(1) Checking the Model and Product Specifications
Check that the model and specifications indicated on the nameplate
attached to the main unit are as ordered.
(2) Packaged Items
Check that the package contains the following items:
●
MU5D: 1
●
RJC sensor (A1167HT): 1
(RJC sensor is not attached for the optional specification
“/RJCN.”)
●
Spacer (for DIN rail mounting): 1
●
Range label: 1
●
User’s Manual (this manual: IM 77J04U05-02E): 1
GENERAL
The MU5D is a plug-in type universal temperature converter that is
connected to an IEC/JIS-standard thermocouple, converts the tem-
perature signals into isolated DC current or DC voltage signals.
IM 77J04U05-02E
Copyrignt© July 2005
3rd Edition Oct. 2007 (YK)
MODEL AND SUFFIX CODES
Model
Output
2: 2 outputs
Power supply
1: 15-40V DC (Operating range: 12 to 48 V)
6: 100-240 V AC/DC (Operating range: 85 to 264 V)
Input signal
U: Thermocouple, RTD, mV
Z: (Custom order)
Customized thermocouple or RTD
Output-1 signal
A: 0 to 20 mA DC
Span is 5 mA or more
B: 0 to 5 mA DC
Span is 1 mA or more
1:
−
10 to
+
10 V DC
Span is 0.1 V or more
2:
−
100 to
+
100 mV DC
Span is 10 mV or more
Z: (Custom order)
Customized current signals or voltage signals
Output-2 signal
A: 4 to 20 mA DC
1: 0 to 10 mV DC
B: 2 to 10 mA DC
2: 0 to 100 mV DC
C: 1 to 5 mA DC
3: 0 to 1 V DC
D: 0 to 20 mA DC
4: 0 to 10 V DC
E: 0 to 16 mA DC
5: 0 to 5 V DC
F: 0 to 10 mA DC
6: 1 to 5 V DC
G: 0 to 1 mA DC
7:
−
10 to
+
10 V DC
Z: (Custom order)
Customized current signals or voltage signals
Optional specification
/SN: Without socket
/RJCN: Without RJC sensor
MU5D -02 - 0 /