Setting parameters, 6list of parameters, 1 setting burnout action – Yokogawa JUXTA MS5 User Manual
Page 4: 2 setting input range, 3 setting output range
4
IM 77J04S05-01E
1st Edition
Jul 29, 2005-00
5. SETTING PARAMETERS
Set the parameters using a PC (VJ77 Parameter Setting Tool) or the
Handy Terminal. Refer to “6. List of Parameters” in this manual and the
User’s Manual for VJ77 PC-based Parameters Setting Tool (IM
77J01J77-01E) or the User’s Manual for JHT200 Handy Terminal (IM
JF81-02E). Parameters are indicated inside the [ ].
5.1
Setting Burnout Action
Set the burnout action in [D43:BURN OUT].
Set “OFF”, “UP”, or “DOWN”.
NOTE
●
Set the burnout action before setting the input range.
Changing the burnout action setting resets the input
range.
●
Turn the adjustment switch counterclockwise to reset
the set value before setting the input range.
5.2
Setting Input Range
Set the input low range in [P16:IN1 LOW RNG], and input high range in
[P17:IN1 HIGH RNG].
(1) Resetting the input range
Select and set “RESET” in [P16:IN1 LOW RNG] or [P17:IN1 HIGH
RNG]. Then the input low range or input high range are reset.
(2) Setting the input low range
Apply the stable signal equivalent to 0% input from the connected
potentiometer. Select and set “EXECUTE” in [P16:IN1 LOW
RNG]. Then the input low range is set automatically.
(3) Setting the input high range
Apply the stable signal equivalent to 100% input from the con-
nected potentiometer. Select and set “EXECUTE” in [P17:IN1
HIGH RNG]. Then the input high range is set automatically.
5.3
Setting Output Range
Set the output range 0% in [D38:OUT1L_RNG], and the output range
100% in [D39:OUT1H_RNG].
NOTE
Changing the output range resets the adjusted value.
6
LIST OF PARAMETERS
A
A07
A54
A56
A58
A60
B
B07
B60
D
D01
D02
D03
D04
D38
D39
D43
D49
D60
P
P16
P17
P26
P27
P60
Q
Q03
Q60
MODEL
TAG NO
SELF CHK
DISPLAY1
OUTPUT1
STATUS
REV NO
MENU REV
SELF CHK
DISPLAY2
OUTPUT1
SELF CHK
SET (I/O)
TAG NO.1
TAG NO.2
COMMENT1
COMMENT2
OUT1 L_RNG
OUT1 H_RNG
BURN OUT
OUT1 DR
SELF CHK
ADJUST
IN1 LOW RNG
IN1 HIGH RNG
OUT1ZERO ADJ
OUT1SPAN ADJ
SELF CHK
TEST
OUT1 TEST
SELF CHK
Model
Tag number
Self-check result
Display1
Output-1
Status *
1
REV No.
MENU REV
Self-check result
Display2
Output-1
Self-check result
Setting (I/O)
Tag number-1
Tag number-2
Comment-1
Comment-2
Output-1 low range
Output-1 high range
Burnout
Direction of output-1 action
Self-check result
Adjustment
Setting of input-1 low range
Setting of input-1 high range
Output-1 zero adjustment
Output-1 span adjustment
Self-check result
Test
Forced output-1
Self-check result
Parameter Display
Item
*1 The displayed status is to let the service staff know the past records of the
product.