beautypg.com

Description of alarm actions, Timing chart of pulse integration operation, 2 settings related to communication function – Yokogawa JUXTA VJQ8 User Manual

Page 4: 3 settings related to alarm output, 1 communication protocol, 2 communication address, 3 baud rate, 4 parity, 5 data length, 6 stop bit

background image

4

IM 77J01Q08-01E 4th Edition

Mar. 02, 2012-00

5.2 Settings Related to Communication

Function

Set the following parameters when output-2 is specified

for communication function. For more information on the

communication function, see the Instruction Manual for VJ Series

Communication Function (IM 77J1J11-01E).

5.2.1 Communication Protocol

Set the communication protocol by selecting from among

PCLINK, PC-LINK WITH SUM, MODBUS ASCII, MODBUS

RTU, and LADDER in

[F01: PROTOCOL].

5.2.2 Communication Address

Set the address number of the isolator numerically in a range

of 1 to 99 in

[F02: ADDRESS].

5.2.3 Baud Rate

Set the baud rate by selecting from among 1200, 2400, 4800,

and 9600 bps in

[F03: BAUD RATE].

5.2.4 Parity

Select and set NONE, EVEN, or ODD in

[F04: PARITY].

5.2.5 Data Length

Select and set 7 bits or 8 bits in

[F05: DATA LEN].

5.2.6 Stop Bit

Select and set 1 bit or 2 bits in

[F06: STOP BIT].

5.2.7 Input Decimal Point Position

Number of digits of decimal places can be set.

Select and set among 0 to 5 digits in

[F07: INPUT DEC PT].

5.3 Settings Related to Alarm Output

Set the following parameters when output-2 is specified for alarm

output.

5.3.1 Alarm Setpoints

Set the alarm setpoints of alarm-1 and alarm-2 in

[E03: SET

POINT1] and [E04: SET POINT2] numerically.

Setting range: A range of 0 to 100% of input range

Setting resolution: 0.1%

5.3.2 Direction of Alarm Action

Select the direction of alarm-1 action and that of alarm-2

action from among HIGH ALM (high-limit alarm) and LOW

ALM (low-limit alarm) and set each in

[E05: ALM1 ACTION]

(direction of alarm-1 action) or

[E06: ALM2 ACTION]

(direction of alarm-2 action).

To activate alarm status when input signal ≥ alarm setpoint,

select HIGH ALM.

To activate alarm status when input signal ≤ alarm setpoint,

select LOW ALM.

5.3.3 Hysteresis

Set alarm-1 and alarm-2 hysteresis, in

[E09: HYSTERESIS1]

and

[E10: HYSTERESIS2]. Hysteresis is a value added to the

alarm setpoint in order for an alarm status to be released (to

normal) after the alarm status has been activated. The alarm

status will be released in the following conditions, depending

on the direction of alarm action.

* When HIGH ALM (high-limit alarm) is set: Alarm is released

when input signal < (alarm setpoint - hysteresis).

* When LOW ALM (low-limit alarm) is set: Alarm is released

when input signal > (alarm setpoint + hysteresis).

Setting range: A range of 0 to 100% of input range

Setting resolution: 0.1%

5.3.4 Alarm ON Delay and Alarm OFF Delay

Set alarm-1 and alarm-2 ON delays in

[E11: ON DELAY1] and

[E12: ON DELAY2] and then alarm-1 and alarm-2 OFF delays

in

[E13: OFF DELAY1] and [E14: OFF DELAY2]. An alarm

ON delay is a delay time from the establishment of alarm

condition to alarm output; an alarm OFF delay is a delay time

from the establishment of return-to-normal condition to output.

Setting range: 0 to 999 seconds

Setting resolution: 1 second (Note that about 0.2 second will

be added to set time to prevent erroneous operation.)

For example, when an alarm ON delay is set to 1 second,

alarm output is generated if alarm status continues for

more than 1 second after the input value exceeds the

alarm setpoint. Further, when an alarm OFF delay is set

to 2 seconds, alarm output is released if normal condition

continues for more than 2 seconds after the input value has

returned to normal from the alarm status.

5.3.5 Direction of Relay Action

Set the direction of relay energizing in alarm-1 normal

condition and alarm-2 normal condition by selecting from

among NRM DEENERGIZED (de-energized under normal

condition) and NRM ENERGIZED (energized under normal

condition) in

[E15: RL1 ACTION] and [E16: RL2 ACTION]

and set them.

6. DESCRIPTION OF ALARM ACTIONS

This chapter describes examples of alarm actions under the

following conditions.

Item

Alarm-1

Alarm-2

Parameter

Setpoint Parameter

Setpoint

Direction of alarm
action

E05: ALM1 ACTION High-limit

alarm

E06: ALM2 ACTION Low-limit

alarm

Alarm setting

E03: SET POINT1

80%

E04 : SET POINT2

15%

Hysteresis

E09: HYSTERESIS1 10%

E10 : HYSTERESIS2 5%

Alarm ON delay

E11: ON DELAY1

1 sec.

E12 : ON DELAY2

3 sec.

Alarm OFF delay

E13: OFF DELAY1

2 sec.

E14 : OFF DELAY2 4 sec.

Description of alarm
actions

The alarm sounds if the

condition where the input value

is 80% or more of high-limit

alarm continues for more than 1

second. After the alarm sounds,

when the condition where

input value is less than 70%of

the high-limit alarm continues

for more than 2 seconds, the

status returns to normal

The alarm sounds if the

condition where the input value

is 15% or less of low-limit

alarm continues for more than

3 seconds. After the alarm

sounds, when the condition

where input value is more than

20% of the low-limit alarm

continues for more than 4

seconds, the status returns to

normal.

Alarm-1 action

Alarm-2 action

Normal

Normal

Normal

Normal

Alarm

Alarm

[%]

0

20

15

40

60

80

100

1 sec.

2 sec.

3 sec.

4 sec.

Alarm-2 hysteresis (5%)

Alarm-1 hysteresis (10%)

Alarm-1 setpoint (80%)

Alarm-2 setpoint (15%)

Elapsed time 1 sec.

[1]

[2]

[3]

[4]

[1]: Alarm status does not continue for more than 1 second after

the alarm conditions are established at alarm-1.

[2]: Normal status does not continue for more than 2 seconds after

the normal conditions are established at alarm-1.

[3]: Alarm status does not continue for more than 3 seconds after

the alarm conditions are established at alarm-2.

[4]: Normal status does not continue for more than 4 seconds after

the normal conditions are established at alarm-2.

Alarm-1

ON delay

Alarm-2

ON delay

Alarm-2

OFF delay

Alarm-1

OFF delay

Alarm conditions

established

Alarm conditions

established

Normal conditions

established

Normal conditions established

High-limit alarm ON

Low-limit alarm ON

High-limit alarm OFF

Low-limit alarm OFF

7. TIMING CHART OF PULSE

INTEGRATION OPERATION

This timing chart shows an example of the integration operation

where input frequency is 0 to 10 Hz and sampling time is 2 sec.

10%

2 sec

0%

ON

ON

ON

ON ON ON ON

ON

Sampling

interval

Analog

output

Input pulse

5%

5%

20%