SAMPLE GUIDE SPECIFICATIONS

Provide a refrigerant leak detection sensor(s) to monitor for R-xxx refrigerant leaks. The sensing element shall be
solid state metal oxide semiconductor type and have a typical life of at least 4 years. The sensor shall be powered
by 24 vdc and have a 4 to 20 mA output signal.

The sensor shall be housed in an industrial style, explosion proof housing and have explosion proof conduit
connections to the housing to maintain system integrity.

NOTE:
1. Refrigerant R744 is Carbon Dioxide (CO

2

) - Use a Toxalert CO220 sensor which has both a digital and a 4

to 20 mA output. See catalog section 3.

2. Refrigerant R717 is Ammonia (NH

3

) - Use a Toxalert Tox-NH

3

/ANA sensor which as a 4 to 20 mA output.

See catalog section 6.

3. Refrigerant R764 is Sulfur Dioxide (SO

2

) - Use a Toxalert Tox-SO

2

/ANA sensor which has a 4 to 20 mA

output. See catalog section 6.

How to order

R-11

= Tox-Rfg/1/M/A

R-113

= Tox-Rfg/1/R/A

R-12

= Tox-Rfg/1/N/A

R-142b = Tox-Rfg/1/S/A

R-22

= Rox-Rfg/1/O/A

R-152a = Tox-Rfg/1/T/A

R-123

= Tox-Rfg/1/P/A

R-500

= Tox-Rfg/1/U/A

R-134a = Tox-Rfg/1/Q/A

R-502

= Tox-Rfg/1/V/A

* For other refrigerants consult factory *