Tox – refrig monitor – Toxalert Tox-Refrig User Manual
Page 4
TOXALERT INTERNATIONAL, INC., P.O. BOX 159, MOUND, MINNESOTA 55364 • 952/472-4541 • 952/472-4960
www.toxalert.com
SPECIFICATIONS
TOX-REFRIG CONTROLLER-
Input Power: 120VAC, 60Hz, 1 Amp(fused)
Warning Setpoint: Field adjustable, factory set
Alarm Setpoint: Field adjustable, factory set
Warning Stage: Visual indication, Form C relay contacts
Alarm Stage: Visual indication, Form C relay contacts
Sensor Malfunction: Visual indication, warning stage
activation, and separate Form C relay contacts
Digital Readout: 3 1/2 digit, red LED, in PPM
Relay Contacts: Rated for 5 Amps @ 120VAC, resistive
load
BACnet: MS/TP communications
Operating Range: 32°F to 120°F (0°C to 49°C)
Mechanical:
Dimensions:14”H x 12”W x 4”D
Classification: NEMA 1
Weight: 12 lbs
TOX-REFRIG/ANA SENSOR: (specs for most Toxalert refrigerant sensors) ─ [Order Sensor Separately]
Method: Semiconductor cell diffusion barrier
type
Range: 15 to 500 PPM
Response: 90% of concentration in less than 30
sec.
Operating Range:
Temp: 14°F to 104°F. (-10°C to 40°C)
Humidity: 5 to 95% non-condensing
Typical Life: Four years in normal service
Maintenance: Periodic calibration
Mechanical:
Dimensions: 6.75”H x 4”W x 3.5”D
Material: Cast aluminum epoxy painted
Classification: Class I Division I Groups
C, D
Weight: 2 lbs.
TOX-REFRIG REVISED 2/12
TOX – REFRIG MONITOR