Specifications, Features, Ventilation control – Toxalert GVU-18 User Manual
Page 2: Options, Gvu series products

MODEL GVU-6, 12, 18 1/06
TOXALERT INTERNATIONAL, INC.,
P.O. BOX 159, MOUND, MINNESOTA 55364 (952) 472-4541 FAX (952) 472-4960
Visit our website at www. toxalert. com
SPECIFICATIONS
Input Power: 120VAC, 60Hz, 1 A (fused)
Relay Contacts: 24 VAC, 2A resistive, 1.5 inductive
Minimum Fan On Time: Adjustable in 5 minute
Finish: Control Unit: Gray enamel
intervals
Enclosure: Nema 1 standard, others available
Dimensions:
GVU-6
20”H x 12”W x 6” D
(508 mm x 305 mm x 152.4 mm)
GVU-12 20”H x 20”W x 6” D
(508 mm x 508 mm x 152.4 mm)
GVU-18 20”H x 24”W x 6” D
(508 mm x 609 mm x 152.4 mm)
FEATURES
• Fully electronic for long life
• User adjustable alarm setting
• Minimum fan run time
• User adjustable 2nd stage activation
• Trouble Free Operation
• Visual indication of high gas concentration
• Operating range meets OSHA std. 1910.1000
VENTILATION CONTROL
Should a high gas concentration occur (above user-adjustable alarm level), an alarm signal from any
sensor unit starts a 30 second delay. Should the concentration persist through the delay period, the
“alarm” clock is activated. The “on” time of this clock, is user-adjustable in discrete settings from 5 to 55
minutes. Upon activation of the “alarm” clock, the “fan-on” relay energizes and remains energized until
the “alarm” clock” times out. Should the high concentration still be above the alarm level, the “fan-on”
relay will remain ON and the “alarm” relay will energize. This condition is maintained until the high
concentration drops.
OPTIONS:
• Audible alarm w/push button audio silence
• Sensor status indicators per sensor
• Fan on indicator
• Second zone of fan control
• Fan override switch
• 7-day time clock
GVU SERIES PRODUCTS:
CONTROLLERS –
GVU-1
Control unit for use with one sensor
GVU-3
Control unit for use with one to three remote sensors
GVU-6
Control unit for use with one to six remote sensors
GVU-12
Control unit for use with one to twelve remote sensors
GVU-18
Control unit for use with one to eighteen remote sensors
REMOTE SENSORS –
GVU-CO
Remote carbon monoxide sensor
GVU-NO
2
Remote nitrogen dioxide sensor
GVU-CO
2
Remote carbon dioxide sensor
GVU-VOC
Remote smoke/air quality sensor
ANNUAL CALIBRATION CHECK IS RECOMMENDED