beautypg.com

Specifications, Features, Ventilation control – Toxalert GVU-18 User Manual

Page 2: Options, Gvu series products

background image

MODEL GVU-6, 12, 18 1/06

TOXALERT INTERNATIONAL, INC.,

P.O. BOX 159, MOUND, MINNESOTA 55364 (952) 472-4541 FAX (952) 472-4960

Visit our website at www. toxalert. com

SPECIFICATIONS

Input Power: 120VAC, 60Hz, 1 A (fused)

Relay Contacts: 24 VAC, 2A resistive, 1.5 inductive

Minimum Fan On Time: Adjustable in 5 minute

Finish: Control Unit: Gray enamel

intervals

Enclosure: Nema 1 standard, others available

Dimensions:
GVU-6

20”H x 12”W x 6” D
(508 mm x 305 mm x 152.4 mm)

GVU-12 20”H x 20”W x 6” D

(508 mm x 508 mm x 152.4 mm)

GVU-18 20”H x 24”W x 6” D

(508 mm x 609 mm x 152.4 mm)

FEATURES

• Fully electronic for long life
• User adjustable alarm setting
• Minimum fan run time
• User adjustable 2nd stage activation

• Trouble Free Operation
• Visual indication of high gas concentration
• Operating range meets OSHA std. 1910.1000

VENTILATION CONTROL

Should a high gas concentration occur (above user-adjustable alarm level), an alarm signal from any
sensor unit starts a 30 second delay. Should the concentration persist through the delay period, the
“alarm” clock is activated. The “on” time of this clock, is user-adjustable in discrete settings from 5 to 55
minutes. Upon activation of the “alarm” clock, the “fan-on” relay energizes and remains energized until
the “alarm” clock” times out. Should the high concentration still be above the alarm level, the “fan-on”
relay will remain ON and the “alarm” relay will energize. This condition is maintained until the high
concentration drops.

OPTIONS:

• Audible alarm w/push button audio silence

• Sensor status indicators per sensor

• Fan on indicator

• Second zone of fan control

• Fan override switch

• 7-day time clock

GVU SERIES PRODUCTS:

CONTROLLERS –
GVU-1

Control unit for use with one sensor

GVU-3

Control unit for use with one to three remote sensors

GVU-6

Control unit for use with one to six remote sensors

GVU-12

Control unit for use with one to twelve remote sensors

GVU-18

Control unit for use with one to eighteen remote sensors

REMOTE SENSORS –
GVU-CO

Remote carbon monoxide sensor

GVU-NO

2

Remote nitrogen dioxide sensor

GVU-CO

2

Remote carbon dioxide sensor

GVU-VOC

Remote smoke/air quality sensor

ANNUAL CALIBRATION CHECK IS RECOMMENDED

This manual is related to the following products: