The AT card (Watlow P/N 08-5422) provides a delayed
SCR turn ON, providing an infinitely variable voltage and
current from full OFF to full ON. The AT card can be
used on resistive, inductive, or Tungsten lamp loads. It
includes a 2-4 second soft start on power up, and a one
second soft start on input signal step change. The AT
also includes a missing half cycle detector to put it into
emergency shutdown (ESD), and retrigger the soft start.
A low signal on the ESD terminals puts the unit into
ESD. The input is factory set for 4-20mA into 250
Ω
. It
can be converted to a voltage input by removing R2 and
readjusting the bias and gain potentiometers for any volt-
age from 0-3V
Î
(dc) to 0-15V
Î
(dc). Without R2, it is a
5K input impedance. See the illustration on the reverse
side.
AT card power supply requirements are 24V
Å
(ac) cen-
ter tap transformer secondary. Transformer primary
must be connected to the same line phase as the heater
load. For example, is the heater is powered by L1 and
L2, then the power transformer must also be connected
to L1 and L2. See the illustration on the reverse side.
Dimensions
Specifications
(1274)
Input
•
Process input factory set @ 4-20mA
Î
(dc)
•
Input impedance 250
Ω
(clip resistor for 5K
Ω
voltage
input), or manual control input
•
Soft start approximately 2-4 seconds upon power-
up, 1 second upon set point change
Output
•
Phase angle control
•
TTL compatible (5V logic) at about 5mA @ 5V. Will
drive one industry standard 3-32V
Î
(dc) input ran-
dom fire SSR. For single phase only.
Line Voltage Power
•
50/60 Hz V~ (ac) line frequency
•
Voltage ±10%, 120, 208, 240, 277, 380, 415, 480V~
(ac). Power transformer is supplied with the AT
card. When ordering, specify power supply voltage
and line frequency.
Line Voltage Compensation
•
10%
∆
in line, 2%
∆
in load in the 30% to 70% power
region.
Input to Output Linearity
•
2%, 30% to 70% power region
Operating Environment
•
32 to 122°F (0 to 50°C)
Storage Temperature
•
-40 to 185°F (-40 to 85°C)
Options
•
Manual control kit for voltage input cards (1K
Ω
potentiometer) #08-5362. Includes dial, knob, 1K
Ω
pot and wiring.
Ordering Information
•
Watlow P/N 08-5422
Watlow Controls
1241 Bundy Blvd., P.O. Box 5580
Winona, MN 55987-5580
Phone: 507-454-5300, Fax: 507-452-4507
0600-0028-0001 Rev D
Made in the U.S.A.
August, 1999
Printed on Recycled Paper
10% Postconsumer Waste
VPAC-AT
Remote Mount Transformer
Data Sheet
(1275)