Control Mode

• Zero cross

Operator Interface

• Command signal input

• Input signal indication LED

Input Command Signal

• Input Type DC1

• Turn ON voltage 4VÎ (dc) max., turn OFF voltage 1VÎ (dc) min.

• Input current: DC typ. 10mA @ 4VÎ (dc), 13mA @ 32VÎ (dc)

• Input Type AC1

• 90-140Vrms, must turn ON at 90 VÅ(ac), must turn OFF

at 10VÅ(ac)

• Input current: 15mA typical @ 120VÅ(ac)

Output Voltage

• 24 volt; 24VÅ(ac) min. to 280VÅ(ac) max.

• 480 volt: 48VÅ (ac) min. to 530VÅ(ac) max.

• 600 volt: 48VÅ (ac) min. to 660VÅ(ac) max. (not available on 18

amp version)

• Off State Leakage

1mA at 25°C/77°F max. for 600VÅ(ac) models; 10mA at

25°C/77°F max. for 24 through 480VÅ(ac) models

• Holding current: 250mA max.

Output Amperage

• See output rating curve on page 1. Ratings are into a resistive

heater load.

Max. surge current

16.6mSec

250

625

1000

24

Output Amperage

34

42

260

625

18

1620

1620

4150

Max. I

2

t for fusing

Agency Approvals

• Class II construction

• UL 508 recognition file number E73741

• CSA file LR 700195

The Series CZR is warranted to be free of defects
in material and workmanship for 24 months after
delivery to the first purchaser for use, providing
that the units have not been misapplied. Since
Watlow has no control over their use, and some-
times misuse, we cannot guarantee against failure.
Watlow's obligations hereunder, at Watlow's option, are limited
to replacement, repair or refund of purchase price, and parts
which upon examination prove to be defective within the
warranty period specified. This warranty does not apply to dam-
age resulting from transportation, alteration, misuse, abuse or
improper fusing.

1. Call Customer Service: 507-454-5300, or fax: 507-452-4507,

for a Return Material Authorization (RMA) number before
returning any item for repair.

2. Make sure the RMA number is on the outside of the carton,

and on all paperwork returned. Ship on a freight prepaid basis.

3. A restocking charge of 20% of the net price applies for all

returned stock controls and accessories in like new condition
and within 120 days after shipment. Non-stock and modified
stock items are not returnable.

4. If the unit is unrepairable, it will be returned to you with a let-

ter of explanation. Repair costs will not exceed 50% of the
original cost.

Specifications

(1992)

Warranty

Ordering Information

(1993)

Recommended Semiconductor Fuses

CZR Model

Fuse*

Fuse Holder

18A

17-8025

17-5110

24A

17-8030

17-5114

34A

17-8040

17-5114

42A

17-8063

17-5122

*Recommended at base rating.

Returns

• 2006/95/EC CE Low Voltage Directive

Output Terminals

• Compression type

• For 18 amp models:

• Maximum wire size 3.0mm (10 AWG), torque to 0.6Nm (5.3

in. lbs.)

• For 24 to 42 amp models:

• Maximum wire size 16.0mm (6 AWG stranded), torque to

1.5-1.7Nm (13-15 in. lbs.)

Operating Environment

• Up to 80˚C/176˚F. See output rating curves for your application.

• 0 to 90% RH, non-condensing.

• Insulation only tested to 3,000 meters.

• Units are suitable for “Pollution degree 2.”

• Cycle time should be less than 3 seconds.

Mounting

Options include DIN rail or standard back panel mounting.

• The DIN rail specification:

DIN EN 50022,

35mm x 7.5mm.

• Min. clipping distance:

34.8mm (1.37 in).

• Max. clipping distance:

35.3mm (1.39 in)

• Mount cooling fins vertical

Weight/Dimensions

• 260g (9.2 oz.)

• 24 to 42 amp models: 100 mm (3.95 in) high x 45 mm (1.75

in) wide x 109 mm (4.3 in) deep

• 18 amp models: 100 mm (3.95 in) high x 22.6 mm (0.89 in)

wide x 99 mm (3.9 in) deep

Specification subject to change without notice.

Part Number

C — — — - A — — V - — — — 0

Control Mode

Z = Zero cross

Output Amperage

18 = 18 amp

24 = 24 amp

34 = 34 amp

42 = 42 amp

Output Voltage

24 = 24 to 280VÅ (ac)

48 = 48 to 530VÅ (ac)

60 = 60 to 660VÅ (ac)

Input Type (Contactor)

DC1 = 4 to 32VÎ (dc)

AC1 = 90 to 140VÅ (ac)

NOTE: Do not use the AC1 input type models with temperature

control outputs that include an AC snubber filter. This could