Rtd (2 wire) wiring diagram, Rtd (3 wire) wiring diagram – Watlow Series 985 User Manual
Page 15

Input Options “2” & " 3 " RTD - 2 Wire
Terminals 12 - 14
ModeI#98 _ A - 2 _ _0-0000
98_A-3_ _0-0000
Jumper#l3to#l4
Input Options “2” & " 3 " RTD - 3 Wire
Terminals 12 - 14
Model# 98_A-2_ _ 0-0000
98_A-3_ _0-0000
.
.
.
.
.
.
-
NOTE:
Long lead lengths create electrical resistance. There will be
a
1° approximate
input error for every 1ohm of lead length resistance when using a two wire RTD.
That resistance, when added to the resistance of the RTD element, can result in
erroneous input to the instrument. To overcome this problem, use
a
three wire
RTD sensor, which compensates for lead length resistance. When extension wire
is used for a three wire RTD, all three extension wires must have the same
electrical resistance. (i.e. same gauge, copper stranded).
Figure 12 -
Input Options "2" &
“3”, RTD (2 wire)
Sensor Wiring.
Figure 13 -
Input Options “2’ &
‘*3”, RTD (3 wire)
Sensor Wiring.
Install and Wire, Chapter 2
WATLOW Series 980/985 User's Manual
15
- 12LS Controller (111 pages)
- 8LS Controller (140 pages)
- 8PID Controller (55 pages)
- Addendum to EZwarePlus (50 pages)
- ANASCAN (62 pages)
- ANASOFT (95 pages)
- ANAWIN 2 (154 pages)
- ANAWIN 3 (23 pages)
- Calibrating Watlow Series 988 Family Process Controls (19 pages)
- CAS (98 pages)
- CAS200 (124 pages)
- CLS (180 pages)
- CLS200 (251 pages)
- CLS200, MLS300 and CAS200 (92 pages)
- Control Console (12 pages)
- CPC400 (230 pages)
- DIN-A-MITE Style A (9 pages)
- DIN-A-MITE Style B (14 pages)
- DIN-A-MITE Style C (22 pages)
- DIN-A-MITE Style D (9 pages)
- DIN-Mount Adapter Instruction Sheet, Rev A (1 page)
- Dual DAC (4 pages)
- EM Gateway (28 pages)
- E-Safe Hybrid Relay Rev B (4 pages)
- E-SAFE II Hybrid Power Switch (4 pages)
- EZwarePlus Programming (264 pages)
- EZ-ZONE PM (111 pages)
- EZ-ZONE PM PID (125 pages)
- EZ-ZONE PM Express Limit (34 pages)
- EZ-ZONE PM Express (35 pages)
- EZ-ZONE PM Integrated Controller (181 pages)
- EZ-ZONE RM Limit Module Rev C (127 pages)
- EZ-ZONE RMA Modul (79 pages)
- EZ-ZONE RMC (236 pages)
- EZ-ZONE RME (124 pages)
- EZ-ZONE RMH (161 pages)
- EZ-ZONE RUI/Gateway (62 pages)
- EZ-ZONE RM-Scanner-Modul (140 pages)
- EZ-ZONE ST (97 pages)
- F4 External Event Board - Rev.B (2 pages)
- HG Series Mercury Displacement Relay (6 pages)
- LogicPro (296 pages)
- Mercury Relay or MDR Retrofit (13 pages)
- MICRODIN (24 pages)
- MICRODIN (106 pages)