Series 920 – Watlow Series 920 Retrofit User Manual
Page 8
![background image](/manuals/359206/8/background.png)
Series 920
Series 920
Line Voltage
Input
Temp Range Control Mode
Action
Output
Set Point
Mounting
Retrofit
See Notes
Below
920A-4CD0-A000
115/230 VAC
Universal
Progammable
Progammable
Sw DC, 6A Relay
Profiling
1/4 DIN
F4SH-CKA0-01RG
3
920A-4CD0-B000
115/230 VAC
Universal
Progammable
Progammable
Sw DC, 6A Relay
Profiling
1/4 DIN
F4SH-CKA0-01RG
3, 16
920A-4DA0-A000
115/230 VAC
Universal
Progammable
Progammable
6A Relay, no output 2
Profiling
1/4 DIN
F4SH-KAA0-01RG
3
920A-4DA0-B000
115/230 VAC
Universal
Progammable
Progammable
6A Relay, no output 2
Profiling
1/4 DIN
F4SH-KAA0-01RG
3, 16
920A-4DB0-A000
115/230 VAC
Universal
Progammable
Progammable
6A Relay, 0.5A SSR
Profiling
1/4 DIN
F4SH-KKA0-01RG
3
920A-4DB0-B000
115/230 VAC
Universal
Progammable
Progammable
6A Relay, 0.5A SSR
Profiling
1/4 DIN
F4SH-KKA0-01RG
3, 16
920A-4DC0-A000
115/230 VAC
Universal
Progammable
Progammable
6A Relay, Sw DC
Profiling
1/4 DIN
F4SH-KCA0-01RG
3
920A-4DC0-B000
115/230 VAC
Universal
Progammable
Progammable
6A Relay, Sw DC
Profiling
1/4 DIN
F4SH-KCA0-01RG
3, 16
920A-4DD0-A000
115/230 VAC
Universal
Progammable
Progammable
6A Relay, 6A Relay
Profiling
1/4 DIN
F4SH-KKA0-01RG
3
920A-4DD0-B000
115/230 VAC
Universal
Progammable
Progammable
6A Relay, 6A Relay
Profiling
1/4 DIN
F4SH-KKA0-01RG
3, 16
920A-4EA0-A000
115/230 VAC
Universal
Progammable
Progammable
15A Triac, no output 2
Profiling
1/4 DIN
F4SH-CAA0-01RG
3
920A-4EA0-B000
115/230 VAC
Universal
Progammable
Progammable
15A Triac, no output 2
Profiling
1/4 DIN
F4SH-CAA0-01RG
3, 16
920A-4EB0-A000
115/230 VAC
Universal
Progammable
Progammable
15A Triac, 0.5A SSR
Profiling
1/4 DIN
F4SH-CKA0-01RG
3
920A-4EB0-B000
115/230 VAC
Universal
Progammable
Progammable
15A Triac, 0.5A SSR
Profiling
1/4 DIN
F4SH-CKA0-01RG
3, 16
920A-4EC0-A000
115/230 VAC
Universal
Progammable
Progammable
15A Triac, Sw DC
Profiling
1/4 DIN
F4SH-CCA0-01RG
3
920A-4EC0-B000
115/230 VAC
Universal
Progammable
Progammable
15A Triac, Sw DC
Profiling
1/4 DIN
F4SH-CCA0-01RG
3, 16
920A-4ED0-A000
115/230 VAC
Universal
Progammable
Progammable
15A Triac, Relay
Profiling
1/4 DIN
F4SH-CKA0-01RG
3
920A-4ED0-B000
115/230 VAC
Universal
Progammable
Progammable
15A Triac, Relay
Profiling
1/4 DIN
F4SH-CKA0-01RG
3, 16
920A-4FA0-A000
115/230 VAC
Universal
Progammable
Progammable
4-20MA, no output 2
Profiling
1/4 DIN
F4SH-FAA0-01RG
920A-4FA0-B000
115/230 VAC
Universal
Progammable
Progammable
4-20MA, no output 2
Profiling
1/4 DIN
F4SH-FAA0-01RG
16
920A-4FB0-A000
115/230 VAC
Universal
Progammable
Progammable
4-20MA, 0.5A SSR
Profiling
1/4 DIN
F4SH-FKA0-01RG
920A-4FB0-B000
115/230 VAC
Universal
Progammable
Progammable
4-20MA, 0.5A SSR
Profiling
1/4 DIN
F4SH-FKA0-01RG
16
920A-4FC0-A000
115/230 VAC
Universal
Progammable
Progammable
4-20MA, Sw DC
Profiling
1/4 DIN
F4SH-FCA0-01RG
920A-4FC0-B000
115/230 VAC
Universal
Progammable
Progammable
4-20MA, Sw DC
Profiling
1/4 DIN
F4SH-FCA0-01RG
16
920A-4FD0-A000
115/230 VAC
Universal
Progammable
Progammable
4-20MA, Relay
Profiling
1/4 DIN
F4SH-FKA0-01RG
3
920A-4FD0-B000
115/230 VAC
Universal
Progammable
Progammable
4-20MA, Relay
Profiling
1/4 DIN
F4SH-FKA0-01RG
3, 16
Note 1: Retrofit controller requires a substitution of a 100 Ohm DIN RTD sensor.
Note 2: Mounting and dimensions of retrofit controller are different. Verify that sufficient panel space and depth is available.
Note 3: Retrofit controller outputs are different. Add external interposing mechanical or solid state relay if applicable.
Note 4: Retrofit controller has a programmable, not fixed set point. Lock set point using controller's lockout parameter.
Note 5: For DIN rail mounting or sub-panel mounting, purchase DIN rail adapter p/n 0822-0586-P001 for 1/32 DIN or p/n 0822-0586-P002 for 1/16 DIN.
Note 6: Add a quencharc suppressor, Watlow p/n 0804-0147-0000, for inductive loads.
Note 7: Retrofit does not have equivalent action (as example, no manual reset)
Note 8: Retrofit controller does not have dual dial scale.
Note 9: Hardware lockout is not available on retrofit.
Note 10: Retrofit controller does not have user selectable line voltage.
Note 11: Retrofit does not support remote set point or retransmit. If wires are on these pins, select a different retrofit.
Note 12: Retrofit controller does not have user selectable control action.
Note 13: Solid state sensor required for humidity. See http://www.vaisala.com
Note 14: Retrofit controller does not have user selectable control mode.
Note 15: Use auxiliay event board A007-1732-F4B8
Note 16: Retrofit communications are different, consult specifications.
Note 17: Verify retrofit input range matches application.
Watlow Controls
4/27/2006
Page 3