Watlow SDA Card Shorted Solid State Relay Detector User Manual

Page 2

background image

To Heater

TB1

2 1

(See below for wiring.)

Load

Line

Fuse

L1

L2

Load

Number of Passes of Load Wire

Current

Through Current Transformer

2 to 3 Amps

5

3 to 4 Amps

4

4 to 5 Amps

3

5 to 10 Amps

2

10 to 40 Amps

1

Load

Semiconductor

Fuse

AC Line

Voltage

DC

Input

Signal

L1

L2

-

+

- +

Input

- +

Output

DC Input

Solid State Relay

2 1

120 V~ (ac)

To Alarm

or Contactor

Customer Supplied Relay

(Philips ECG PIY 1055 or equivalent)

TB1

SDA Board

08-5386

Current

Transformer

30A to 20mA

Figure 3 - SDA Card Wiring

Table 1 - Application of 16-0231 Current Transformer

Figure 2 - Three Dimensional View of Wiring

NOTE: The triac connection
between connector TB1 pins
1 and 2 is closed when a
shorted SSR condition is
detected. This output is rated
24 to 240V~ (ac), 300mA @
25°C, 125mA @ 80°C.