American Power Conversion 5000 VA User Manual
Page 11
9
N
OTE
:
S
ETTINGS ARE MADE THROUGH SUPPLIED
P
OWER
C
HUTE SOFTWARE
,
OPTIONAL
S
MART
S
LOT
ACCESSORY CARDS
,
OR
T
ERMINAL
M
ODE
.
F
UNCTION
F
ACTORY
D
EFAULT
U
SER
S
ELECTABLE
C
HOICES
D
ESCRIPTION
Low Bypass Point
160 VAC
Output Voltage Setting
200 VAC:
160 - 185 VAC
208 VAC:
160 - 190 VAC
220 VAC:
160 - 195 VAC
230 VAC:
160 - 200 VAC
240 VAC:
160 - 205 VAC
Minimum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.
Output Voltage
XLJ models:
200 VAC
XLT models:
208 VAC
XLTW models:
220 VAC
XLI models:
230 VAC
200, 208, 220,
230, 240 VAC
Allows the user to select the on
on-line output voltage.
50 ± 3 Hz
50 ± 1 Hz
50 ± 0.1 Hz
60 ± 3 Hz
60 ± 1 Hz
60 ± 0.1 Hz
Output Frequency
Automatic
50 ± 3 Hz or
60 ± 3 Hz
50 ± 3 Hz or 60 ± 3 Hz
Sets the allowable UPS output
frequency. Whenever possible,
the output frequency tracks the
input frequency.
Number of External
Battery Packs
0
0 to 100
Defines the number of external
connected battery packs for
proper run time prediction.
Bypass Acceptable
Not required
Required/ Not required
Phase and frequency lock
required/not required before the
UPS will switch to bypass.