Onfigurable, Tems – American Power Conversion 5000 VA User Manual
Page 10
8
U
SER
C
ONFIGURABLE
I
TEMS
N
OTE
:
S
ETTINGS ARE MADE THROUGH SUPPLIED
P
OWER
C
HUTE SOFTWARE
,
OPTIONAL
S
MART
S
LOT
ACCESSORY CARDS
,
OR
T
ERMINAL
M
ODE
.
F
UNCTION
F
ACTORY
D
EFAULT
U
SER
S
ELECTABLE
C
HOICES
D
ESCRIPTION
Automatic Self-Test
On start-up and
every 14 days,
thereafter
On start-up and every 7
days thereafter
On start-up and every 14
days thereafter
On start-up only
No self-test
Set the interval at which the
UPS will execute a self-test.
Date of Last Battery
Replacement
Manufacture date
Date of
battery replacement
Reset this date when you replace
the battery modules.
Minimum Run time
Before Return from
Shutdown
0 seconds
0 to 3600 s of run time
Specify the minimum run time
following a low battery
shutdown, before powering
connected equipment.
Audible Alarm
Setting
ON
ON, OFF
Enable or disable all alarms
permanently.
Simple Shutdown
Delay
90 seconds
0 to 1800 s
Set the interval between the time
when the UPS receives a simple
shutdown command and the
actual shutdown.
Simple Low Run
Time Warning
150 seconds
0 to 1800 s
Change the warning interval
default to a higher setting if the
operating system requires a
longer interval for shutdown.
The low battery warning beeps
are continuous when 150
seconds of run time remain.
High Bypass Point
255 VAC
Output Voltage Setting
200 VAC:
210 - 280 VAC
208 VAC:
220 - 280 VAC
220 VAC:
235 - 280 VAC
230 VAC:
245 - 280 VAC
240 VAC:
255 - 280 VAC
Maximum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.