beautypg.com

Onfigurable, Tems – American Power Conversion 5000 VA User Manual

Page 10

background image

8

U

SER

C

ONFIGURABLE

I

TEMS

N

OTE

:

S

ETTINGS ARE MADE THROUGH SUPPLIED

P

OWER

C

HUTE SOFTWARE

,

OPTIONAL

S

MART

S

LOT

ACCESSORY CARDS

,

OR

T

ERMINAL

M

ODE

.

F

UNCTION

F

ACTORY

D

EFAULT

U

SER

S

ELECTABLE

C

HOICES

D

ESCRIPTION

Automatic Self-Test

On start-up and
every 14 days,
thereafter

On start-up and every 7
days thereafter
On start-up and every 14
days thereafter
On start-up only
No self-test

Set the interval at which the
UPS will execute a self-test.

Date of Last Battery
Replacement

Manufacture date

Date of
battery replacement

Reset this date when you replace
the battery modules.

Minimum Run time
Before Return from
Shutdown

0 seconds

0 to 3600 s of run time

Specify the minimum run time
following a low battery
shutdown, before powering
connected equipment.

Audible Alarm
Setting

ON

ON, OFF

Enable or disable all alarms
permanently.

Simple Shutdown
Delay

90 seconds

0 to 1800 s

Set the interval between the time
when the UPS receives a simple
shutdown command and the
actual shutdown.

Simple Low Run
Time Warning

150 seconds

0 to 1800 s

Change the warning interval
default to a higher setting if the
operating system requires a
longer interval for shutdown.
The low battery warning beeps
are continuous when 150
seconds of run time remain.

High Bypass Point





255 VAC

Output Voltage Setting
200 VAC:

210 - 280 VAC
208 VAC:
220 - 280 VAC
220 VAC:
235 - 280 VAC
230 VAC:
245 - 280 VAC
240 VAC:
255 - 280 VAC

Maximum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.

This manual is related to the following products: