A-1

INSTALLATION

POWER WAVE

®

S350

A-1

TECHNICAL SPECIFICATIONS - POWER WAVE

®

S350

RECOMMENDED INPUT WIRE AND FUSE SIZES

1

INPUT

VOLTAGE / PHASE/

FREQUENCY

200-208/1/50/60
200-208/3/50/60

230/1/50/60
230/3/50/60

380-415/3/50/60

460/3/50/60
575/3/50/60

TIME DELAY FUSE

OR BREAKER

2

AMPERAGE

80
50
80
45
30
25
20

CORD SIZE

3

AWG SIZES

(mm

2

)

6 (13)
8 (10)
4 (16)
8 (10)
12 (4)
12 (4)

14 (2.5)

MAXIMUM

INPUT AMPERE RAT-

ING AND DUTY CYCLE

60A, 100%
39A, 40%
67A, 30%
35A, 40%
19A, 40%
17A, 40%
14A, 40%

RATED OUTPUT

POWER SOURCE-INPUT VOLTAGE AND CURRENT

Model

K2823-3

Duty Cycle

40% rating

100% rating

300

Amps

29

Volts

350

Amps

31.5

Volts

320

Amps

30

Volts

INPUT

VOLTAGE/PHASE/

FREQUENCY

200-208/1/50/60

230/1/50/60

200-208/3/50/60

230/3/50/60

380-415/3/50/60

460/3/50/60
575/3/50/60

Input Amperes

(1 Phase in parenthesis)

39/35/19/17/14

(60/67

1

/NA/NA/NA)

31/28/15/14/11

(60/53/NA/NA/NA)

Idle Power

300 Watts Max.

(fan on)

Power Factor @

Rated Output

.95

Input Voltage ± 10%

208/230/400*460/575

50/60 Hz

(*includes 380V to 413V)

1. Based on U.S. National electrical Code

2. Also called " inverse time" or "thermal / magnetic" circuit breakers; circuit breakers that have a delay in trip-

ping action that decreases as the magnitude of the current increases

3. Type SO cord or similar in 30° C ambient

4. When operating on these inputs, the line cord should be changed to an input conductor of 6 AWG or larger.

* On 230 Volt / 1 phase inputs the max. rating is at a duty cycle of 30%, except for GTAW processes.

GMAW

40%*

60%

60%

100%

300 Amps / 29 Volts

250

Amps

30

Volts

325

Amps

33

Volts

275

Amps

31

Volts

SMAW

40%*

100%

250 Amps / 30 Volts

300

Amps

22 Volts

350

Amps

24 Volts

325

Amps

23Volts

GTAW-DC

40%

60%

100%