Vanguard RFD-200 S3 User Manual
Page 7
![background image](/manuals/354202/7/background.png)
REV 1 RFD-200 S3 USER’S MANUAL
4
1.2
RFD-200 S3 Technical Specifications
Table 1. RFD-200 S3 Technical Specifications
TYPE
Portable relay test set
INPUT POWER
100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz
PHYSICAL SPECIFICATIONS
Dimensions: 16.8”W x 12.6”H x 12”D (42.7 cm x 32.0 cm x 30.5 cm);
Weight: 35 lbs (15.9 kg)
AMPERE METER INPUT
RANGES
Internal input range: 0 – 250 A; Accuracy: 2% of reading ±10 mA
External AC input range: 0 – 6A; Accuracy: 1% of reading ±10mA
External DC input range: 0 – 6A; Accuracy: 0.5% of reading ±1 count
Measurement Method: True RMS for AC
VOLT METER INPUT RANGE
0 – 600.0V; AC accuracy: 1% of reading ±1 count; DC accuracy 0.5% of
reading ±1 count
Measurement Method: True RMS for AC
POWER RESISTORS
5 Ω/50 W, 1 Ω/50 W, 25 Ω/50 W, 100 Ω/50 W, 500 Ω/50 W
DRY CONTACT OUTPUT
3A, 240 Vac or 120 Vdc
AUXILIARY POWER SUPPLIES
24 Vdc @ 1 A, 48 Vdc @ 0.25 A, 124 Vdc @ 0.125 A
SAFETY
Designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 standards
ENVIRONMENT
Operating: -10°C to +50°C (+15°F to +122°F);
Storage: -30°C to +70°C (-22°F to +158°F)
HUMIDITY
90% RH @ 40°C (104°F) non-condensing
ALTITUDE
2,000 m (6,562 ft) to full safety specifications
OPTIONS
Transportation case
WARRANTY
One year on parts and labor
NOTE
The above specifications are valid at nominal operating voltage and at a
temperature of 25
°C (77°F). Specifications may change without prior notice.