REV 1 RFD-200 S3 USER’S MANUAL

4

1.2

RFD-200 S3 Technical Specifications

Table 1. RFD-200 S3 Technical Specifications

TYPE

Portable relay test set

INPUT POWER

100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz

PHYSICAL SPECIFICATIONS

Dimensions: 16.8”W x 12.6”H x 12”D (42.7 cm x 32.0 cm x 30.5 cm);
Weight: 35 lbs (15.9 kg)

AMPERE METER INPUT

RANGES

Internal input range: 0 – 250 A; Accuracy: 2% of reading ±10 mA
External AC input range: 0 – 6A; Accuracy: 1% of reading ±10mA
External DC input range: 0 – 6A; Accuracy: 0.5% of reading ±1 count
Measurement Method: True RMS for AC

VOLT METER INPUT RANGE

0 – 600.0V; AC accuracy: 1% of reading ±1 count; DC accuracy 0.5% of
reading ±1 count
Measurement Method: True RMS for AC

POWER RESISTORS

5 Ω/50 W, 1 Ω/50 W, 25 Ω/50 W, 100 Ω/50 W, 500 Ω/50 W

DRY CONTACT OUTPUT

3A, 240 Vac or 120 Vdc

AUXILIARY POWER SUPPLIES

24 Vdc @ 1 A, 48 Vdc @ 0.25 A, 124 Vdc @ 0.125 A

SAFETY

Designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 standards

ENVIRONMENT

Operating: -10°C to +50°C (+15°F to +122°F);
Storage: -30°C to +70°C (-22°F to +158°F)

HUMIDITY

90% RH @ 40°C (104°F) non-condensing

ALTITUDE

2,000 m (6,562 ft) to full safety specifications

OPTIONS

Transportation case

WARRANTY

One year on parts and labor

NOTE

The above specifications are valid at nominal operating voltage and at a
temperature of 25

°C (77°F). Specifications may change without prior notice.