Installation instructions inc2, 2 installation - configuration, Check lan b – TREND INC2 User Manual
Page 7: Configure, Close panel/covers
7
INC2 Installation Instructions TG200231Issue 1/E Draft 2 09/11/06
Installation Instructions
INC2
O
I
I N C 2
?
I N C 2
?
J 7
E T 1
J 1 6
D e v B
J 1 5
D e v A
J 9
J 8
L a n B
L a n A
T X -
T X +
R X -
R X +
T X -
T X +
R X -
R X +
LAN B / IWRK
LAN B / IWRK
11
Check Lan B
Not if RS232 receiver/transmitter
connected to Dev B
b
TXB
(yellow)
a
RXB
(yellow)
c
OKB
(green)
INC2 Faulty
Check network cabling
for short circuits with a
multimeter (NOT Megger)
Network Address Invalid
0, 2, 3 or >119
OKB
OKB
INC2
Check baud rate. Power up
other nodes until faulty node
is found (OK
). Correct
fault.
INC2
Q
X
3.2
Installation - Configuration
(Continued)
13
Configure
Network Engineering Manual 92-1735
IQ Configuration Manual 90-1533
INC2 Data Sheet TA200209
Select from lanmap or set addresses as below:
• If on local Lan, or autodialled Lan, set Lan = 0, address = 126 (Note address used for old INC, Lan 126, address 126, still works)
• If using Internetwork, or autodialled remote Lan, set Lan = switch setting, address = 126
Top Menu
I N C 2
U s e r a d d R e s s
R
e.g.
select addRess module
to eXit module having
changed parameter
to Quit module and
discard changes
12
Close panel/covers
J 7
E T 1
J 1 6
D e v B
J 1 5
D e v A
Recommend use of SET
INC2/USA: The unit is UL rated as
'UL916 accessory to open energy
management equipment'.
Note that a PIN may be required to make changes in configuration mode. If the PIN has been forgotten the user should contact Trend Technical
Support quoting the generator number (User module) whereupon a default PIN will be supplied. This will only work during the same configuration
mode session i.e. the utility must not be exited between reading the generator and entering the default PIN. After the PIN is entered a new
PIN should be set up and remembered.