1 installation - configuration, Check network, Configure alarm language – TREND NBOX(B)_PNC2 User Manual
Page 7: Check system, Close mbox
2 - 3
NBOX(B)/PNC2 Printer Node Controller Installation Instructions TG200266 Issue 1/C 21/07/04
Installation Instructions - Configuration
NBOX(B)/PNC2
O
I
NBOX(B)/PNC2
?
NBOX(B)/PNC2
?
2.1 Installation - Configuration
(continued)
T -
T +
R -
R +
L A N A
T -
T +
R -
R +
L A N A
T X
R X
O K
D T R B
D T R A
C T S B
C T S A
J1
3
J1
2
14
Check Network
(Lan A)
b
TX
a
RX
c
OK
✘
PNC2 faulty
Check Network cabling for
short circuits with a
multimeter (NOT Megger)
Network Address invalid
0, 2, 3 or >119
OK
OK
NBOX(B)/PNC2
Check baud rate
Power up other nodes until
faulty node is found
(OK
). Correct fault.
(yellow)
(yellow)
(green)
PNC2
15
Configure Alarm Language
The PNC2 will automatically set its alarm language to that of the other nodes on the local Lan if possible (otherwise stays in English). It may be changed
if required:
Note that if the PNC2 is reset by power up or on change of address or baud rate, the PNC2 will automatically set its language
Recommend use of PowerTool
or Wupdn
if required
Set language by R(P=x)
where x defines language as follows:
x=0 English, =1 Spanish, =2 Finnish, =3 Swedish, =4 Norwegian, =5 Danish, =6 German, =7 Italian, =8 Portuguese, =9 French.
IQ Configuration Manual 90-1533
PNC2 Data Sheet TA200263
PowerTool Manual TE200163
Wupdn Manual TE200162
16
Check System
PNC2
IQ
! alarm
! alarm
17
Close MBOX
if fitted in ENCLS/MBOX/IQ22x
a
b
Lan