Netb/linc installation instructions, 2 installation - configuration, Lonworks – TREND NETB_LINC User Manual
Page 6

6
NETB/LINC Installation Instructions TG200632 Issue 1/C 15/11/06
NETB/LINC
Installation Instructions
LINC
LINC
Lan
LonWorks
IQL
LONC
11
Check LINC on LonWorks
(Check LonWorks, LINC, and LINC,
or LONC, or IQL)
Lon OK (green)
LINC
Flashes every 24 s, ON after
1½ mins
or
or
and
12
Close Panel
NETB/LINC/FTT/24
only for UL rating
The unit is UL rated as 'UL916,
accessory to open energy
management equipment.'
LINC
LonWorks
Lan
I/N
13
Configure LINC
LINC
LonWorks
Lan
e.g.
R
select addRess module
address 126,
local Lan
address 126,
Lan number
set by
address
switch
SET
SET Manual TE200147
top menu :
or
to eXit module having changed parameter
X
to Quit module and discard changes
Q
Note that the LINC can be configured across LonWorks (using
another LINC) with TARP is set to Yes (default) in both LINCs
(see step 14)
3.2 Installation - Configuration
(Continued)
LINC
X
Switch On
Replace Side Covers
8
9
replace screws
7
Replace Main Cover
Push cover on
O
I
slide in
O
I
10
Check Current Loop Network
Lan OK (green)
LINC Faulty
Check network cabling
for short circuits with a
multimeter (NOT Megger)
Lan OK
Lan OK
Check baud rate. Power up
other nodes until faulty node
is found (OK ). Correct
fault.
NETB/LINC
if address < 100, current loop Lan
if address = > 100, current loop Internetwork (Segment A)