Specifications – JuiceGoose P90 Series User Manual
Page 42

P90 USER’S MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion Corporation (Rev 8/29/13)
Page 42
SPECIFICATIONS
120V MODEL
P90-1000
P90-1500
P90-2000
P90-3000
INPUT
Voltage
120 VAC (85-150V) @ full load
Capacity VA (W)
1000 VA
(900 W)
1500 VA
(1350 W)
2000 VA
(1800 W)
3000 VA
(2700 W)
Frequency
40 - 70 Hz
Power Factor
≥ 0.99 @ normal voltage @ full load
Topology
Online
ECO Mode
Increases efficiency to 98%
EPO
Normally closed
OUTPUT
Voltage
120 VAC ± 1% battery mode (adjustable to
100/110/115/120VAC)
Frequency
57 - 63 Hz
THD (full load)
≤ 2% linear load (8% max battery mode before shutdown)
Wave form
Sine wave, 0 ms transfer time
Load Power Factor
0.9
Efficiency
86-88% (AC mode); 83-85% (Battery mode)
Auto Restart
Yes
Start on Battery
Yes
Rated Current
8.3A
12.5A
16.67A
25.0A
Overload Capacity
125% for 2 min; 150% for 10 sec; > 150% 1 sec
Crest Factor
5:1 at full load
BATTERY
Battery Type
(2) 12V 9AH
/ 24V
(3) 12V 9AH /
36V
(4) 12V 9AH
/ 48V
(6) 12V 9AH
/ 72V
sealed maintenance-free in hot-swappable trays
Backup Time
3 min 45 sec
4 min 41 sec
3 min 50 sec 4 min 15 sec
Charge Current
1A
Recharge Time
< 4 hours to 90%