Operations, Button operation – JuiceGoose P90 Series User Manual
Page 25

P90 USER’S MANUAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Xtreme Power Conversion Corporation (Rev 8/29/13)
Page 25
OPERATIONS
Button Operation
Button
Function
ON/MUTE Button
Turn on the UPS: Press and hold the button more than 2 seconds to turn on
the UPS.
Mute the alarm: After the UPS is turned on in battery mode, press and hold
this button for at least 5 seconds to disable or enable the alarm system. This
feature will not work when warnings or errors occur.
Up key: Press this button to display the previous selection in UPS setting
mode.
Switch to UPS self-test mode: Press and hold ON/MUTE button for 5
seconds to enter UPS self-testing while in AC mode.
OFF/ENTER Button
Turn off the UPS: Press and hold the button more than 2 seconds to turn off
the UPS. The UPS will be in standby mode under normal power or transfer
to bypass mode if the Bypass enable setting is set by pressing this button.
Confirm selection key: Press this button to confirm selection in UPS setting
mode.
SELECT Button
Switch LCD message: Press this button to change the LCD message for input
voltage, input frequency, battery voltage, output voltage, and output
frequency.
Setting mode: Press and hold this button for 5 seconds to enter the UPS
setting mode when UPS is off.
Down key: Press this button to display the next selection in UPS setting
mode.
ON/Mute + Select
Button
Switch to Bypass mode: When the utility power is normal, press ON/MUTE
and SELECT buttons simultaneously for 5 seconds. The UPS will then enter
Bypass mode. The Bypass mode will be disabled when the input voltage is
out of acceptable range.