Electric models only – American Dryer Corp. T20 User Manual
Page 14

14
JLA Limited
113428-9
Electric Models Only
All electrically heated dryers must be connected to the electric
service shown on the dryer’s data label. The connecting wires
must be properly sized to handle the rated current.
Electrical Service Specifications
Gas and Steam Models Only
2/12/08
ELECTRICAL SERVICE SPECIFICATIONS (PER POCKET)
IMPORTANT:
NOTES: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.
When fuses are used they must be dual element, time delay, current
limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse
value, by applying either local and/or National Electrical Codes to
listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type
ONLY. For others, calculate/verify correct breaker size according to
appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz
50 Hz
T20 Stack Gas
120
1ш
2
8.9
—
15
200
1ш
2
7.7
7.8
15
208
1ш
2
7.6
—
15
220
1ш
2
—
7.4
15
230
1ш
2
—
7.3
15
240
1ш
2
7.2
7.0
15
T30 Stack Gas
120
1ш
2
10.3
—
15
200
1ш
2
8.7
8.8
15
208
1ш
2
8.4
—
15
220
1ш
2
8.1
8.1
15
230
1ш
2
—
7.4
15
240
1ш
2
7.7
7.0
15
T30 Stack Steam
120
1ш
2
9.3
—
15
208
1ш
2
—
6.0
15
220
1ш
2
—
5.5
15
230
1ш
2
—
5.4
15
240
1ш
2
5.1
—
15
ELECTRICAL SERVICE SPECIFICATIONS (PER POCKET)
IMPORTANT:
NOTES: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.
When fuses are used they must be dual element, time delay, current
limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse
value, by applying either local and/or National Electrical Codes to
listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY. For
others, calculate/verify correct breaker size according to appliance
amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz
50 Hz
T20 Stack
200 (5.6 kW)
1ø
2
32.7
32.7
45
208 (4.1 kW)
1ø
2
24.2
—
35
208 (6.1 kW)
1ø
2
34.0
—
45
220 (6.8 kW)
1ø
2
35.6
—
45
230 (5.0 kW)
1ø
2
—
26.4
35
230 (7.4 kW)
1ø
2
—
36.8
50
240 (5.4 kW)
1ø
2
27.1
—
35
240 (8.1 kW)
1ø
2
38.4
38.4
50
208 (6.5 kW)
3ø
3
22.7
—
30
240 (7.5 kW)
3ø
3
22.6
—
30
380 (6.8 kW)
3ø
4
—
15.0
20
400 (7.5 kW)
3ø
4
—
15.5
20
416 (8.1 kW)
3ø
4
—
15.8
20
T30 Stack
200 (12.5 kW)
1ø
2
68.4
67.7
90
208 (7.9 kW)
1ø
2
43.8
—
60
208 (13.5 kW)
1ø
2
70.7
—
90
230 (8.3 kW)
1ø
2
—
41.3
60
230 (12.4 kW)
1ø
2
—
59.1
80
240 (9.0 kW)
1ø
2
42.7
—
60
240 (13.5 kW)
1ø
2
61.5
—
80
208 (13.5 kW)
3ø
3
43.3
—
60
220 (11.3 kW)
3ø
3
35.3
—
50
230 (12.4 kW)
3ø
3
—
36.5
50
240 (13.5 kW)
3ø
3
37.7
—
50
380 (11.3 kW)
3ø
4
22.8
22.6
40
400 (12.4 kW)
3ø
4
—
23.1
40
416 (13.5 kW)
3ш
4
—
23.7
40
2/12/08