E. rotating the flue adapter – HTP MC120 User Manual
Page 44

44
LP-171 Rev. 4.10.14
Figure 24
– Piping Exhaust around Obstructions – Suggested Condensate Removal
E. ROTATING THE FLUE ADAPTER
The flue adapter on the top of the heater can be rotated 180 degrees to position the air inlet in the optimum location for most venting
and air inlet needs. The flue adapter MUST be positioned before the exhaust vent is connected to the adapter.
NOTE: Once the exhaust vent is glued to the flue adapter it can no longer be moved.
NOTE: DO NOT glue optional polypropylene vent system.
To rotate the flue adapter:
1. Remove the black heater cover.