beautypg.com

Hochiki FB-1 User Manual

Page 16

background image

Page 16 of 19

ESP FIREbeam – Installation Manual

 2011 Hochiki Europe (UK) Ltd

2-3-0-1340/ISS2/DEC11

Phase

- When using multiple beams that face each other the beam output signals

could phase together and can cause unreliable readings, by setting each beam to
phase differently alleviates this problem. Use the

right

and

left

keys to give

each beam a different phase pattern (length between output beam sample times)
you can choose between 0 (default setting) and 6. Press

enter

to return to

‘Mode Change’ or

down

to go to ‘Hysteresis’.

Hysteresis

- Changing the hysteresis will change the delay in returning from a

fire state back to a normal state. For example, the beam is factory set at 15% so if
the beam falls into fire at 65% (35% threshold) it has to recover 15% to 80%
before it returns to normal. This action prevents small fluctuations in returned
signal causing the beam to fall in and out of a fire state. This can be adjusted
between 1% and 40% by using the

right

and

left

keys. Press

enter

to

return to ‘Mode Change’ or

down

to go to ‘Comp Fire – Fault’.

Press

enter

to return to ‘Mode Change’.