WARNING
The washer-extractor should be connected to an individual branch
circuit not shared with lighting or other equipment.
4
Electrical Specifications WF235, IWF235, IWF055, CWF235, CWF055
235 liters / 55 pounds
Boiler Fed/Steam Heat
Electric Heat
Code
Voltage
Cycle
Phase
Wire
Full
Load Amps
Recommended Circuit
Breaker (US-market)
AWG/mm2
kW Standard
Heating Elements
Full
Load Amps
Recommended
Circuit Breaker (US-
market)
AWG/mm2
US NON-US
US NON-US
N
440-480 50/60
3
3+PE
6
15
10
14/2.5
6x3 kW
32
40
40
8/10.0
P
380-415 50/60
3
3+N+PE 16
20
20
12/4.0
43
50
50
8/10.0
Q
200-240 50/60
3
3+PE
16
20
20
12/4.0
62
70
70
4/25.0
X
200-240 50/60
1/3
2/3+PE
16
20
20
12/4.0
N/A N/A
N/A
N/A
Alternative Electric Heat Options
N
440-480 50/60
3
3+PE
3x3 kW +
3x2 kW
27
30
32
10/6.0
P
380-415 50/60
3
3+N+PE
40
50
50
8/10.0
Q
200-240 50/60
3
3+PE
56
60
60
6/16.0
X
200-240 50/60
1/3
2/3+PE
N/A N/A
N/A
N/A
N
440-480 50/60
3
3+PE
3x3 kW +
3x4 kW
36
40
40
8/10.0
P
380-415 50/60
3
3+N+PE
48
50
50
8/10.0
Q
200-240 50/60
3
3+PE
N/A N/A
N/A
N/A
X
200-240 50/60
1/3
2/3+PE
N/A N/A
N/A
N/A
N
440-480 50/60
3
3+PE
6x2 kW
23
30
25
10/6.0
P
380-415 50/60
3
3+N+PE
35
40
40
8/10.0
Q
200-240 50/60
3
3+PE
48
50
50
8/10.0
X
200-240 50/60
1/3
2/3+PE
N/A N/A
N/A
N/A
N
440-480 50/60
3
3+PE
6x4 kW
40
50
50
8/10.0
P
380-415 50/60
3
3+N+PE
53
60
60
8/10.0
Q
200-240 50/60
3
3+PE
N/A N/A
N/A
N/A
X
200-240 50/60
1/3
2/3+PE
N/A N/A
N/A
N/A
Table 5